| Plan Review Notes For Permit 04011273 |
| Permit Number |
04011273 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2004-12-23 00:00:00 | ****CORRECTIONS***** | | | TRUSS SUBMITTAL | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)BCLL OF 10PSF REQUIRED FOR ATTICS | | | WITHOUT STORAGE, 30PSF FOR ATTICS WITH | | | STORAGE, FBC TABLE 1604.1. | | | | | | 2.)ORIGINAL SIGNATURE REQUIRED, NOT A | | | STAMP, FAC61G15-23.002. | | | | | | 3.)TITLE BLOCK REQUIRED WITH ALL | | | INFORMATION REQUIRED BY | | | FAC61G15-23.002. | | | | | | 4.)SOME SHEETS ARE NOT SIGNED AND | | | SEALED.ALL DOCUMENTS SUBMITTED FOR | | | PUBLIC RECORD PREPARED BY AND ENGINEER | | | ARE TO BE SIGNED AND SEALED, | | | FAC61G15-23.002. | | | | | | 5.)PLEASE ADVISE AS TO THE STATUS FOR | | | THE ENGINEERING FOR THE METAL ROOF | | | (PROVISO WHEN THE PERMIT WAS ISSUED). |
|