| Plan Review Notes For Permit 04011273 |
| Permit Number |
04011273 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-21 00:00:00 | FAILED | | | ---------------------------------------- | | | BALANCED RETURN AIR IS REQUIRED FROM ALL | | | HABITABLE AREAS OF HOUSE PER FBC(M)601.4 | | | | | | THERE IS NO VISIBLE MEANS OF RETURN AIR | | | IN THE FOLLOWING AREAS: | | | | | | 1ST FL- ALL AREAS OUTSIDE OF BEDROOMS | | | ARE SEPARATED FROM R/A BY POCKET | | | DOOR. A SEPARATE MEANS OF RETURN | | | IS REQUIRED IN LIBRARY. POCKET | | | DOORS SEPARATING FAMILY ROOM | | | AND KITCHEN FROM RETURN SHOULD | | | ALSO BE ACCOUNTED FOR. | | | | | | 2ND FL- STUDY AND DRESSING AREA SHOW NO | | | VISIBLE MEANS OF BALANCED R/A. | | | | | | PLEASE CALL ME IF YOU HAVE ANY QUESTIONS | | | RONALD J REGUEIRO 561-805-6734 |
|