| 2004-02-09 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALLED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT.PER 110.9/110.10. |
| | |
| | 2} PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 3} THERE ARE 4 AHU'S ON THE ELECTRICAL |
| | PLAN AND 3 ON THE MECHANICAL PLAN, |
| | PLEASE CORRELATE. ALSO SEE KW RATINGS, |
| | BOTH PLANS. |
| | |
| | 4} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 5} THE PLAN SHOWS AN ELEVATER BUT NO |
| | EQUIPMENT FOR IT IS IN THE LOAD |
| | CALCULATIONS. |
| | |
| | 6} PLEASE ADD SMOKE DETECTORS TO COMPLY |
| | WITH 8-1.4.1.6.2. NFPA-72 AND 905.2.2 |
| | FBC.SEE REVIEWED PLAN. |
| | |
| | 7} ALL BATH RECEPTACLES MUST COMPLY |
| | WITH210.8(A)(1),GFI. |
| | |
| | 8} A RECEPTACLE NEEDS TO BE INSTALLED |
| | INTHE "POWDER ROOM",SHEET 14.PER |
| | 210.52(D). |
| | |
| | 9} RECEPTACLES IN THE LAUNDRY ROOM AND |
| | THE SCREENED VERANDA BY THE SINK TO BE |
| | GFI PER 210.8(A)(7). |
| | |
| | 10} ADD A RECEPTACLE AT THE CONDENSING |
| | UNITS TO COMPLY WITH 210.63. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |