Plan Review Notes
Plan Review Notes For Permit 04011273
Permit Number 04011273
Review Stop E
Sequence Number 1
Notes
Date Text
2004-02-09 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT.PER 110.9/110.10.
  
 2} PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 3} THERE ARE 4 AHU'S ON THE ELECTRICAL
 PLAN AND 3 ON THE MECHANICAL PLAN,
 PLEASE CORRELATE. ALSO SEE KW RATINGS,
 BOTH PLANS.
  
 4} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 5} THE PLAN SHOWS AN ELEVATER BUT NO
 EQUIPMENT FOR IT IS IN THE LOAD
 CALCULATIONS.
  
 6} PLEASE ADD SMOKE DETECTORS TO COMPLY
 WITH 8-1.4.1.6.2. NFPA-72 AND 905.2.2
 FBC.SEE REVIEWED PLAN.
  
 7} ALL BATH RECEPTACLES MUST COMPLY
 WITH210.8(A)(1),GFI.
  
 8} A RECEPTACLE NEEDS TO BE INSTALLED
 INTHE "POWDER ROOM",SHEET 14.PER
 210.52(D).
  
 9} RECEPTACLES IN THE LAUNDRY ROOM AND
 THE SCREENED VERANDA BY THE SINK TO BE
 GFI PER 210.8(A)(7).
  
 10} ADD A RECEPTACLE AT THE CONDENSING
 UNITS TO COMPLY WITH 210.63.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026