Notes
Date Text
2004-03-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.)CITY OF WEST PALM BEACH MUNICIPAL
 CODE, 94-546 (B)(1), LOWEST FLOOR
 SHALL BE ELEVATED TO 6" ABOVE THE BASE
 FLOOD ELEVATION.THE SURVEY SHOULD BE
 REVISED (NOW SHOWS 7).ALSO NOTE
 PROPOSED FINISHED FLOOR ELEVATION ON THE
 FOUNDATION PLAN.
  
 4.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 5.)PROVIDE INFORMATION FOR THE
 FIREPLACE AND CHIMNEY.FACTORY BUILT
 CHIMNEYS AND FIREPLACES SHALL BE TESTED
 IN ACCORDANCE WITH AND MEET THE
 REQUIREMENTS OF UL127.
  
 6.)ADDITIONAL FEES DUE, SEE ATTACHED
 BZ04011273 (VALUE ADJUSTMENT, RADON).
  
 7.)THE NORTH PROPERTY LINE ON THE SITE
 PLAN SHOULD HAVE A DIMENSION OF 188.65'.
  
 8.)THE ARCHITECTURE LICENSE NUMBER
 FOR AMES DESIGN INTERNATIONAL IS TO BE
 ON EACH SHEET.THE PRINTED NAME AND
 LICENSE NUMBER OF THE PERSON SEALING THE
 PLAN IS TO BE ON EACH SHEET.THE
 NUMBER AAC001720 IS NULL AND VOID,
 REMOVE FROM THE PLAN.THE SEAL IS TO
 BE DATED AS WELL AS SIGNED.FAC61G1-
 16.003, 004.
  
 9.)THERE ARE REFERENCES ON THE PLAN TO
 THE ELEVATOR MFGR INSTRUCTIONS AND SHOP
 DRAWINGS.PLEASE PROVIDE INSTALLATION
 INSTRUCTIONS.INDICATE METHOD OF
 ATTACHMENT FOR THE ELEVATOR.
  
 10.)PROVIDE A DETAIL FOR THE
 COFFERED CEILING, INCLUDING FIREBLOCKING
 705.3.1.
  
 11.)ONE BATHROOM AT GRADE LEVEL SHALL
 HAVE A DOOR WITH A 29" CLEAR OPENING
 FBC11-11(1).
  
 12.)GUARDRAILS/STAIRRAILS ARE TO
 COMPLY WITH FBC1608.2.2.
  
 13.)THE DECORATIVE WOOD RAILING SHOWN
 ON SHEET 6 DOES NOT APPEAR TO COMPLY
 WITH FBC1015.3.IS THIS A SOLID PANEL?
  
 14.)TYPICAL STAIR HANDRAIL DETAIL IS
 TO COMPLY WITH FBC1015.3 EXCEPTION 1.
  
 15.)SEPARATE PERMIT REQUIRED FOR GAS.
  
 16.)SHEET 11, TRUSS ANCHORING SCHEDULE
 META24 DESIGN UPLIFT EXCEEDS THE PRODUCT
 LIMITATION IN THE 2004 CATALOG.CHECK
 ALL CONNECTORS.
  
 17.)SHEET 13, CITY OF WEST PALM BEACH
 IS NOT IN THE HIGH VELOCITY ZONE (NOTE
 3B).
  
 18.)NOTE 4, DESIGN LIVE LOAD, SHEET
 13, PLEASE NOTE THAT THIS IS A DWELLING,
 NOT AN APARTMENT.
  
 19.)NOTE 10, SHEET 13 REFERS TO
 PREFAB CONCRETE FLOOR SYSTEM.OTHER
 DETAILS REFER TO WOOD FLOOR TRUSSES.
 ADDRESS.
  
 20.)SMOKE DETECTORS REQUIRED IN
 ACCORDANCE WITH FBC905.2.2.
  
 21.)THE WINDOW BUCK IS TO EXTEND
 BEYOND THE FRAME FBC1707.4.4.2.
  
 22.)PROVIDE A VALUE FOR THE WORK IN
 THE GARAGE.
  
 23.)PROVIDE THE DIMENSION FROM THE
 GARAGE TO THE PROPERTY LINE.PROVIDE
 THE DESIGN PRESSURE FOR THE GARAGE
 DOOR.
  
 24.)THE ENERGY CALCS GIVE A TOTAL
 UNDER AIR SQUARE FOOTAGE OF 3844; THE
 AREA CALCS ON SHEET 4 GIVE TOTAL A/C AS
 3631.CLARIFY.
  
 25.)FLORIDA STATEWIDE, LOCAL OR SITE
 SPECIFIC PRODUCT APPROVALS REQUIRED.
 WWW.FLORIDABUILDING.ORG.IF AVAILABLE,
 PRINT THE FLORIDA STATEWIDE PRODUCT
 APPROVAL AND INDICATE THE PRODUCT YOU
 ARE USING, AS WELL AS THE TEST REPORT
 LINK IF AVAILABLE.IF A STATEWIDE
 APPROVAL IS NOT AVAILABLE, SUBMIT AN
 APPLICATON FOR LOCAL PRODUCT APPROVAL.
  
 26.)PROVIDE A STRUCTURAL DETAIL FOR
 THE STAIRS, INCLUDING FIREBLOCKING
 FBC2305.1.4(3).
  
 27.)PROVIDE A DRAFTSTOP SCHEDULE
 (FLOOR FRAMING PLAN).
  
 28.)PROVIDE A DETAIL FOR THE TRELLIS
 BALCONY.
  
 29.)PROVIDE INFORMATION/PRODUCT
 APPROVAL FOR THE DECORATIVE SIDING AT
 TOWER, REAR ELEVATION, SHEET 6.
  
 30.)PROVIDE THE SIZE AND LOCATION OF
 THE ATTIC ACCESS, FBC2309.6-7.
  
 31.)ROOF SHEATHING NOTES, #18 SHEET 13
 ZONE 3 IS TO BE 4" O.C. EDGES, CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FBC
 2306.1.
  
 32.)INDICATE WHICH PRODUCT YOU ARE
 USING FOR THE GARAGE DOOR.
  
 33.)THE PRODUCT APPROVAL SUBMITTED
 FOR FIXED GLASS HAS A LIMITATION OF
 +-60 FOR HEAT STR. 3/16 GLASS, IMPACT.
 SOME FIXED GLASS WINDOWS ON THE PLAN
 HAVE A DESIGN PRESSURE OF -63.7.
 ADDRESS.
  
 34.)PROVIDE DESIGN PRESSURE FOR THE
 ROOF.NOTE THAT THE PRODUCT APPROVAL
 SUBMITTED HAS A MAX DESIGN PRESSURE OF
 -62.5.
  
 35.)DETAIL 19, SHEET 18, REFERS TO
 SFBC AND PBC BUILDING CODES.THE
 GOVERNING CODE IS FBC.
  
 36.)DETAIL 4-16, PRIVACY WALL FOOTER
 CANNOT ENCROACH THE PROPERTY LINE.
  
 37.)DETAIL 3-16, SPECIFY LOAD
 REQUIREMENT, DIAMETER OF EYE BOLTS,
 LENGTH.
  
 38.)DETAIL 2-16, STUCCO OVER WIRE
 LATH IN A VERTICAL APPLICATION TO BE
 7/8", FBC2504.2.2, ASTM C926.
  
 39.)PROVIDE THE INSTALLATION
 INSTRUCTIONS FOR THE GARAGE DOOR.
  
 40.)DETAIL 16-17, SBP6 IS NOT IN THE
 SIMPSON CATALOG.NAILING OF SP6
 CONFLICTS WITH THE CATALOG.
  
 41.)DETAIL 26-18, ELEVATOR MOTOR
 DETAIL REFERS TO MFGR SPECS AND SHOP
 DRAWINGS, PLEASE PROVIDE.
  
 42.)PROVIDE A SCHEDULE LISTING THE
 CONNECTORS AND THE FLORIDA PRODUCT
 APPROVAL NUMBER.
  
 43.)DETAIL 21-18 REFERS TO SBC.THE
 GOVERNING CODE IS FBC.
  
 44.)SOFFIT VENTS TO COMPLY WITH FBC
 2309.7.
  
 WHEN RESUBMITTING, CLEARLY INDICATE ALL
 CHANGES.REPLACE REVISED PAGES AND
 SUBMIT OLD SHEETS SEPARATELY.A
 TRANSMITTAL LETTER EXPLAINING HOW EACH
 ITEM WAS ADDRESSED WILL EXPEDITE PLAN
 REVIEW.