| Date |
Text |
| 2004-03-09 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 |
| | |
| | 3.)CITY OF WEST PALM BEACH MUNICIPAL |
| | CODE, 94-546 (B)(1), LOWEST FLOOR |
| | SHALL BE ELEVATED TO 6" ABOVE THE BASE |
| | FLOOD ELEVATION.THE SURVEY SHOULD BE |
| | REVISED (NOW SHOWS 7).ALSO NOTE |
| | PROPOSED FINISHED FLOOR ELEVATION ON THE |
| | FOUNDATION PLAN. |
| | |
| | 4.)PROVIDE A SOILS INVESTIGATION |
| | REPORT. |
| | |
| | 5.)PROVIDE INFORMATION FOR THE |
| | FIREPLACE AND CHIMNEY.FACTORY BUILT |
| | CHIMNEYS AND FIREPLACES SHALL BE TESTED |
| | IN ACCORDANCE WITH AND MEET THE |
| | REQUIREMENTS OF UL127. |
| | |
| | 6.)ADDITIONAL FEES DUE, SEE ATTACHED |
| | BZ04011273 (VALUE ADJUSTMENT, RADON). |
| | |
| | 7.)THE NORTH PROPERTY LINE ON THE SITE |
| | PLAN SHOULD HAVE A DIMENSION OF 188.65'. |
| | |
| | 8.)THE ARCHITECTURE LICENSE NUMBER |
| | FOR AMES DESIGN INTERNATIONAL IS TO BE |
| | ON EACH SHEET.THE PRINTED NAME AND |
| | LICENSE NUMBER OF THE PERSON SEALING THE |
| | PLAN IS TO BE ON EACH SHEET.THE |
| | NUMBER AAC001720 IS NULL AND VOID, |
| | REMOVE FROM THE PLAN.THE SEAL IS TO |
| | BE DATED AS WELL AS SIGNED.FAC61G1- |
| | 16.003, 004. |
| | |
| | 9.)THERE ARE REFERENCES ON THE PLAN TO |
| | THE ELEVATOR MFGR INSTRUCTIONS AND SHOP |
| | DRAWINGS.PLEASE PROVIDE INSTALLATION |
| | INSTRUCTIONS.INDICATE METHOD OF |
| | ATTACHMENT FOR THE ELEVATOR. |
| | |
| | 10.)PROVIDE A DETAIL FOR THE |
| | COFFERED CEILING, INCLUDING FIREBLOCKING |
| | 705.3.1. |
| | |
| | 11.)ONE BATHROOM AT GRADE LEVEL SHALL |
| | HAVE A DOOR WITH A 29" CLEAR OPENING |
| | FBC11-11(1). |
| | |
| | 12.)GUARDRAILS/STAIRRAILS ARE TO |
| | COMPLY WITH FBC1608.2.2. |
| | |
| | 13.)THE DECORATIVE WOOD RAILING SHOWN |
| | ON SHEET 6 DOES NOT APPEAR TO COMPLY |
| | WITH FBC1015.3.IS THIS A SOLID PANEL? |
| | |
| | 14.)TYPICAL STAIR HANDRAIL DETAIL IS |
| | TO COMPLY WITH FBC1015.3 EXCEPTION 1. |
| | |
| | 15.)SEPARATE PERMIT REQUIRED FOR GAS. |
| | |
| | 16.)SHEET 11, TRUSS ANCHORING SCHEDULE |
| | META24 DESIGN UPLIFT EXCEEDS THE PRODUCT |
| | LIMITATION IN THE 2004 CATALOG.CHECK |
| | ALL CONNECTORS. |
| | |
| | 17.)SHEET 13, CITY OF WEST PALM BEACH |
| | IS NOT IN THE HIGH VELOCITY ZONE (NOTE |
| | 3B). |
| | |
| | 18.)NOTE 4, DESIGN LIVE LOAD, SHEET |
| | 13, PLEASE NOTE THAT THIS IS A DWELLING, |
| | NOT AN APARTMENT. |
| | |
| | 19.)NOTE 10, SHEET 13 REFERS TO |
| | PREFAB CONCRETE FLOOR SYSTEM.OTHER |
| | DETAILS REFER TO WOOD FLOOR TRUSSES. |
| | ADDRESS. |
| | |
| | 20.)SMOKE DETECTORS REQUIRED IN |
| | ACCORDANCE WITH FBC905.2.2. |
| | |
| | 21.)THE WINDOW BUCK IS TO EXTEND |
| | BEYOND THE FRAME FBC1707.4.4.2. |
| | |
| | 22.)PROVIDE A VALUE FOR THE WORK IN |
| | THE GARAGE. |
| | |
| | 23.)PROVIDE THE DIMENSION FROM THE |
| | GARAGE TO THE PROPERTY LINE.PROVIDE |
| | THE DESIGN PRESSURE FOR THE GARAGE |
| | DOOR. |
| | |
| | 24.)THE ENERGY CALCS GIVE A TOTAL |
| | UNDER AIR SQUARE FOOTAGE OF 3844; THE |
| | AREA CALCS ON SHEET 4 GIVE TOTAL A/C AS |
| | 3631.CLARIFY. |
| | |
| | 25.)FLORIDA STATEWIDE, LOCAL OR SITE |
| | SPECIFIC PRODUCT APPROVALS REQUIRED. |
| | WWW.FLORIDABUILDING.ORG.IF AVAILABLE, |
| | PRINT THE FLORIDA STATEWIDE PRODUCT |
| | APPROVAL AND INDICATE THE PRODUCT YOU |
| | ARE USING, AS WELL AS THE TEST REPORT |
| | LINK IF AVAILABLE.IF A STATEWIDE |
| | APPROVAL IS NOT AVAILABLE, SUBMIT AN |
| | APPLICATON FOR LOCAL PRODUCT APPROVAL. |
| | |
| | 26.)PROVIDE A STRUCTURAL DETAIL FOR |
| | THE STAIRS, INCLUDING FIREBLOCKING |
| | FBC2305.1.4(3). |
| | |
| | 27.)PROVIDE A DRAFTSTOP SCHEDULE |
| | (FLOOR FRAMING PLAN). |
| | |
| | 28.)PROVIDE A DETAIL FOR THE TRELLIS |
| | BALCONY. |
| | |
| | 29.)PROVIDE INFORMATION/PRODUCT |
| | APPROVAL FOR THE DECORATIVE SIDING AT |
| | TOWER, REAR ELEVATION, SHEET 6. |
| | |
| | 30.)PROVIDE THE SIZE AND LOCATION OF |
| | THE ATTIC ACCESS, FBC2309.6-7. |
| | |
| | 31.)ROOF SHEATHING NOTES, #18 SHEET 13 |
| | ZONE 3 IS TO BE 4" O.C. EDGES, CITY OF |
| | WEST PALM BEACH AMENDMENTS TO THE FBC |
| | 2306.1. |
| | |
| | 32.)INDICATE WHICH PRODUCT YOU ARE |
| | USING FOR THE GARAGE DOOR. |
| | |
| | 33.)THE PRODUCT APPROVAL SUBMITTED |
| | FOR FIXED GLASS HAS A LIMITATION OF |
| | +-60 FOR HEAT STR. 3/16 GLASS, IMPACT. |
| | SOME FIXED GLASS WINDOWS ON THE PLAN |
| | HAVE A DESIGN PRESSURE OF -63.7. |
| | ADDRESS. |
| | |
| | 34.)PROVIDE DESIGN PRESSURE FOR THE |
| | ROOF.NOTE THAT THE PRODUCT APPROVAL |
| | SUBMITTED HAS A MAX DESIGN PRESSURE OF |
| | -62.5. |
| | |
| | 35.)DETAIL 19, SHEET 18, REFERS TO |
| | SFBC AND PBC BUILDING CODES.THE |
| | GOVERNING CODE IS FBC. |
| | |
| | 36.)DETAIL 4-16, PRIVACY WALL FOOTER |
| | CANNOT ENCROACH THE PROPERTY LINE. |
| | |
| | 37.)DETAIL 3-16, SPECIFY LOAD |
| | REQUIREMENT, DIAMETER OF EYE BOLTS, |
| | LENGTH. |
| | |
| | 38.)DETAIL 2-16, STUCCO OVER WIRE |
| | LATH IN A VERTICAL APPLICATION TO BE |
| | 7/8", FBC2504.2.2, ASTM C926. |
| | |
| | 39.)PROVIDE THE INSTALLATION |
| | INSTRUCTIONS FOR THE GARAGE DOOR. |
| | |
| | 40.)DETAIL 16-17, SBP6 IS NOT IN THE |
| | SIMPSON CATALOG.NAILING OF SP6 |
| | CONFLICTS WITH THE CATALOG. |
| | |
| | 41.)DETAIL 26-18, ELEVATOR MOTOR |
| | DETAIL REFERS TO MFGR SPECS AND SHOP |
| | DRAWINGS, PLEASE PROVIDE. |
| | |
| | 42.)PROVIDE A SCHEDULE LISTING THE |
| | CONNECTORS AND THE FLORIDA PRODUCT |
| | APPROVAL NUMBER. |
| | |
| | 43.)DETAIL 21-18 REFERS TO SBC.THE |
| | GOVERNING CODE IS FBC. |
| | |
| | 44.)SOFFIT VENTS TO COMPLY WITH FBC |
| | 2309.7. |
| | |
| | WHEN RESUBMITTING, CLEARLY INDICATE ALL |
| | CHANGES.REPLACE REVISED PAGES AND |
| | SUBMIT OLD SHEETS SEPARATELY.A |
| | TRANSMITTAL LETTER EXPLAINING HOW EACH |
| | ITEM WAS ADDRESSED WILL EXPEDITE PLAN |
| | REVIEW. |