| Plan Review Notes For Permit 04011169 |
| Permit Number |
04011169 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-05-12 00:00:00 | BUILDING REVIEW PROVISO: | | | 1-A)PROVIDE COMPLETE PRODUCT APPROVAL | | | FOR FRENCH DOORS WITH SIDELITES AND | | | TRANSOM ABOVE SINGLE ASSEMBLY AS SHOWN | | | ON PLANS UNDER A SEPARATE PERMIT. | | | B)PROVIDE PRODUCT APPROVAL FOR FIXED | | | GLASS WITH LONG DIMENSION AS SHOWN ON | | | PLANS (PROVIDE THIS ON ABOVE PERMIT). | | | C)PROVIDE COMPLETE INFORMATION FOR ENTRY | | | DOORS PRODUCT APPROVAL AS WELL. | | | 2-CEILING INSTALLATION AT ENTRY AND REAR | | | PORCHES: CLARIFY WHAT'S A 1"X2" 16 GA | | | PNEUMATIC FASTENER AS SPECIFIED ON | | | PLANS. SEC. 104.2.1.2 CITY AMENDMENTS | | | TO FBC 2001. | | | 3-PROVIDE CURRENT UL LISTING & COMPLETE | | | SPECS FOR FIREPLACE. SEC 2806 FBC 2001 | | | 4-SPECIFY MIN. 7/8" STUCCO THICKNESS AT | | | FRAMED WALLS AS REQUIRED BY ASTM C-926 | | | 5-COMPLETE INFORMATION ON DETAIL F/6: | | | SPECIFY HOW MUCH EMBEDMENT IS REQ'D | | | FOR ANCHORS AT BOTTOM PLATE. SECTION | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
|