| 2004-03-12 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-DESIGN CRITERIA: INCLUDE THE ATTIC |
| | LIVE LOAD. 30PSF OR 10PSF. SEE TABLE |
| | 1604.1 FBC 2001. |
| | 3-PROVIDE BBQ UL LISTING AND SPECS. |
| | SECTION 2808 FBC 2001. |
| | 4-PROVIDE STRUCTURAL BUCK DETAIL FOR |
| | ENTRY DOORS SHOWING SIZE OF BUCK REQ'D |
| | TO CLOSE GAP GIVEN THE OPENING SIZE. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 5-ROOF SHEATHING NOTE ON DRAWING A3: |
| | A)REVISE MINIMUM THICKNESS. SEE TABLE |
| | 2306.1 CITY AMENDMENTS TO FBC 2001 |
| | B)SEE FIGURE 1606.2(C) FBC 2001 FOR ROOF |
| | AREAS TO BE CONSIDERED ZONE 3 AND |
| | REVISE NOTE AS REQUIRED. |
| | 6-PROVIDE DETAIL/SPECS FOR CEILING INSTA |
| | LLATION AT ENTRY AND REAR PORCH. SEE |
| | ASTM C-926 AND ASTM C-1063 AS REQUIRED |
| | BY SEC. 2504.2 FBC 2001. |
| | 7-REVISE ENERGY CALCULATIONS. SEE SEC. |
| | 604.1.A.1 CHAPTER 13 FBC 2001 FOR |
| | AREA TO BE CONSIDERED FOR UNDER ATTIC |
| | AREA. |
| | 8-PROVIDE FLORIDA OR LOCAL PRODUCT APPRO |
| | VAL FOR: A)ALL STRUCTURAL CONNECTORS. |
| | B)FIXED WINDOWS WITH SIZE AS SHOWN ON |
| | PLANS. EG. SEE KITCHEN WINDOW. |
| | C)PROVIDE PRODUCT APPROVAL FOR FRENCH |
| | DOORS WITH TRANSOM ABOVE ASSEMBLY AS |
| | SHOWN ON PLAN. |
| | 9-SPECIFY ROOF TILE FASTENERS AS REQ'D |
| | BY SEC. 104.2.1.1 CITY AMENDMENTS TO |
| | FBC 2001 AND SEC. 1606.3 FBC 2001. |
| | 10-PROVIDE UL LISTING AND COMPLETE SPECS |
| | FOR FIREPLACE. SEC. 2806 FBC 2001. |
| | 11-DESIGN PRESSURES FOR OPENINGS SHOWN |
| | ON SEPARATE SHEET DON'T MATCH THOSE |
| | SHOWN ON PLANS. REVISE AS REQUIRED. |
| | 12-SPECIFY SIZE AND REINFORCEMENT FOR |
| | CONCRETE PAD NUMBER 4 FOR STEEL COLS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 13-SPECIFY FASTENERS FOR 2X4 BLOCKING AT |
| | ARCHED & OVAL FRAMING DETAIL. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 14-SPECIFY 7/8" MIN. STUCCO THICKNESS AT |
| | FRAMED AREAS AS REQUIRED BY ASTM C-926 |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |