| Notes |
| Date |
Text |
| 2004-03-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 BUILDING | | | | | | 1) OVERFLOW SCUPPERS SHALL BE A MINIMUM | | | OF 4" IN HEIGHT AND SHALL BE PLACED IN | | | WALLS OR PARAPETS WITH THE INLET FLOW | | | LINE NOT LESS THAN 2" ABOVE THE ROOF | | | SURFACE, EXCLUDING SUMPS, OR MORE THAN | | | 4" ABOVE THE ROOF SURFACE. 32 SQUARE | | | INCHES REQUIRED FOR EACH SCUPPER TO | | | DRAIN 1/2 AREA OF ROOF. SECTION 1503.4.2 | | | SUBMIT A DETAIL FOR SCUPPERS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|