| Plan Review Notes For Permit 04011062 |
| Permit Number |
04011062 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-31 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A-1 SINK IN COPY ROOM SHALL COM- | | | PLY WITH SECTION 11-4.24 AND ALL SUBSEC- | | | TIONS. SUBMIT DETAIL. DOOR SHALL NOT | | | SWING INTO CLEAR FLOOR SPACE REQUIRED | | | FOR ANY FIXTURE. | | | 2) TABLE 403.1 REQUIRES A DRINKING | | | FOUNTAIN. IF AVAILABLE IN THE COMMON | | | AREA, CALL OUT ON PLANS. | | | 3) COPY ROOM SINK SHALL NOT DRAIN INTO | | | THE HORIZONTAL WET VENT OF THE BATHROOM | | | FIXTURES. 909.1 - CONNECT SINK DOWN- | | | STREAM OF BATHROOM FIXTURES ON FLOOR | | | PLAN AND RISER DIAGRAM. | | | 4) SUBMIT MANUF SPEC SHEET FOR INSTA- | | | HOT. SHALL BE LISTED BY APPROVED TESTING | | | AGENCY. | | | 5) PLUMBING FIXTURE SCHEDULE, NO SINK IS | | | SHOWN FOR COPY ROOM SINK. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|