Plan Review Notes
Plan Review Notes For Permit 04011062
Permit Number 04011062
Review Stop P
Sequence Number 1
Notes
Date Text
2004-01-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 SINK IN COPY ROOM SHALL COM-
 PLY WITH SECTION 11-4.24 AND ALL SUBSEC-
 TIONS. SUBMIT DETAIL. DOOR SHALL NOT
 SWING INTO CLEAR FLOOR SPACE REQUIRED
 FOR ANY FIXTURE.
 2) TABLE 403.1 REQUIRES A DRINKING
 FOUNTAIN. IF AVAILABLE IN THE COMMON
 AREA, CALL OUT ON PLANS.
 3) COPY ROOM SINK SHALL NOT DRAIN INTO
 THE HORIZONTAL WET VENT OF THE BATHROOM
 FIXTURES. 909.1 - CONNECT SINK DOWN-
 STREAM OF BATHROOM FIXTURES ON FLOOR
 PLAN AND RISER DIAGRAM.
 4) SUBMIT MANUF SPEC SHEET FOR INSTA-
 HOT. SHALL BE LISTED BY APPROVED TESTING
 AGENCY.
 5) PLUMBING FIXTURE SCHEDULE, NO SINK IS
 SHOWN FOR COPY ROOM SINK.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]