| Plan Review Notes For Permit 04010955 |
| Permit Number |
04010955 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-05-05 00:00:00 | ***** REDLINED ***** | | | | | | ARC FAULT PROECTION IS UNDER 2002 NEC | | | 210.12. PLANS NOTES MENTION 99 NEC | | | REQUIRMENTS. | | | NOET #14 ALSO MENTIONS SD'S TO BE | | | WIRED INTO KIT/BATH LTS. | | | THIS WOULD REQ' ARC FAULT PROTECTION | | | ALSO. |
|