| 2004-02-13 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-PROVIDE COMPLETE INFORMATION FOR STORM |
| | SHUTTERS OR APPLY FOR SEPARATE PERMIT. |
| | 2-PROVIDE FLORIDA OR LOCAL PRODUCT APPRO |
| | VAL FOR: A)ROOF TILE. |
| | B)ENTRY DOORS WITH DWGS THAT WERE SUBMI- |
| | TTED FOR FLORIDA PRODUCT APPROVAL. |
| | **NOTE: IF DOOR IS GOING TO BE USED AS |
| | MEANS OF ESCAPE WHEN SHUTTERS ARE UP, |
| | THEN NEED TO HAVE MISSILE IMPACT GLASS |
| | OR SOLID DOORS. |
| | C)SIDE SWING DOOR WITH DWGS THAT MATCH |
| | FLORIDA PRODUCT APPROVAL REPORT. |
| | D)ARCHED AND RECTANGULAR FIXED WINDOWS |
| | WITH DWGS THAT MATCH FLORIDA PRODUCT |
| | APPROVAL. |
| | E)SINGLE HUNG WINDOWS WITH DWGS THAT |
| | MATCH FLORIDA PRODUCT APPROVAL REPORT. |
| | F)ALL STRUCTURAL CONNECTORS. |
| | |
| | 3-PROVIDE COMPLETE DETAIL AND SPECS FOR |
| | CONSTRUCTION OF ARCHED OPENINGS. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 4-PROVIDE COMPLETE DETAIL AND SPECS FOR |
| | INSTALLATION OF SLIDING GLASS DOORS & |
| | TRANSOM ABOVE ASSEMBLY JOINED BY THE |
| | HORIZONTAL STRUCTURAL MULLION. SPECIFY |
| | ALL FASTENERS. SECTION 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 5-NEED 5/8" MIN. STUCCO THICKNESS AT |
| | WOOD FRAMED AREAS. ASTM C-926. REVISE |
| | ALL DETAILS/SPECS AS REQ'D. |
| | 6-SPECIFY WWM SUPPORTS AND SPACING IN |
| | CONCRETE SLAB OR SPECIFY JOINTS. |
| | SEC. 1909.3 FBC 2001. |
| | 7-SPECIFY FOOTING SIZE AND REINFORCING |
| | FOR F5 CONCRETE PAD. SEE FOUNDATION |
| | PLAN. SEC. 104.2.1.2 CITY AMENDMENTS |
| | 8-REVISE DETAIL 38/S1. NEED 12" MINIMUM |
| | BELOW GRADE. SEC. 1804.1.3 FBC 2001. |
| | 9-SHEET C1: UPDATE CONCRETE NOTES. SEE |
| | COMMENTS ON PLAN AND CHAPTER 35 FBC/01 |
| | 10-SHEET A-5: UPDATE GENERAL NOTES. SEE |
| | COMMENTS ON PLANS. |
| | 11-SHEET S-1: CLARIFY TYPE OF COLUMN AT |
| | BAY WINDOW. SEE COMMENTS ON PLAN. |
| | 12-SHEET S-2: A)ROOF TILE ATTACHMENT |
| | DIAPHRAGM IS TAKEN FROM SBC 1997.NEED |
| | TO UPDATE AS REQUIRED. SEE FBC 2001 |
| | SEC. 1606.3 AND SEC. 104.2.1.1 CITY |
| | AMENDMENTS TO FBC 2001. |
| | B)SEE COMMENTS ON PLANS. REVISE AS REQ'D |
| | 13-SHEET S-3: PROVIDE ONLY DETAILS THAT |
| | APPLY TO THIS PROJECT. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 805-6712. |