Notes
Date Text
2004-03-04 00:00:00DENIED
  
 1) REVISE NOTE #11 UNDER PLAN NOTES ON
 C1 TO INCLUDE AREAS IN WIND BORNE DEBRIS
 REGIONS WHICH ALSO REQUIRED IMPACT
 PROTECTION FOR GLAZED OPENINGS. SEE
 FBC 1606.1.4.
  
 2) REVISE NOTE #15 UNDER FRAMING NOTES
 ON C1 TO SPECIFY THAT HIGH RIB METAL
 LATH IS REQUIRED TO BE ATTACHED AT EACH
 RIB (4"OC) PER ASTM C 1063.
  
 3) SPECIFY THE TRUSS BOTTOM CORD LIVE
 LOAD ON THE PLANS. FBC TABLE 1604.1
 REQUIRES ATTICS WITHOUT STORAGE TO HAVE
 A LIVE LOAD OF 10 PSF AND 30 PSF FOR
 ATTICS WITH STORAGE.
  
 4) ONE HOUR FIRE RATED GLASS BLOCK IS
 REQUIRED ON THE ZERO LOT LINE. PLEASE
 SPECIFY THIS ON THE PLANS.
  
 5) SOME OF THE WINDLOAD PRESSURES AND
 OPENING SIZES ARE MISSING FROM THE RIGHT
 ELEVATION ON A4.
  
 6) REVISE THE SLIDING GLASS DOOR BUCK
 DETAIL TO STATE THAT THEY ARE FASTENED
 THROUGH THE BUCK AND NOT TO THE BUCK.
 SEE FBC 1707.4.4.2.
  
 7) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 1/2" ANCHOR BOLTS FOR THE GARAGE DOOR
 BUCKS ON A4.
  
 8) SPECIFY ON THE PLANS THAT THE DOOR
 FROM THE GARAGE TO CONDITIONED SPACE IS
 INSULATED OR SOLID CORE AS REQUIRED BY
 FBC CHAPTER 13 SECTION 603.
  
 9) REVISE THE SEMCO TRUSS CONNECTOR
 SPECIFIED IN DETAIL 9 ON A5 TO A CURRENT
 ANCHOR WITH STATE OR LOCAL PRODUCT
 APPROVAL.
  
 10) REVISE THE TRUSS CONNECTOR SCHEDULE
 ON A6 TO VALUES THAT DO NOT INCLUDE A
 ONE-THIRD INCREASE FOR THE STEEL
 CALCULATIONS WHICH IS NO LONGER ALLOWED
 BY FBC 1609.4. SEE CURRENT TRUSS
 CONNECTOR CATALOGS. VERIFY THAT ANCHORS
 SPECIFIED ON ROOF FRAMING PLAN WILL
 WORK WITH ADJUSTED ANCHOR VALUES.
  
 11) THE INSTALLATION DRAWING SUBMITTED
 FOR THE GARAGE DOOR IS FOR A 9' WIDE
 DOOR AND THE ONE SHOWN ON THE PLANS IS
 16' WIDE. SUBMIT THE APPROPRIATE
 INSTALLATION DRAWINGS.
  
 12) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 13) THE STORM PANEL INSTALLATION
 SCHEDULE APPEARS TO BE IN ERROR. THE
 ANCHOR SPACING OF 6" SHOULD BE FOR ITEM
 #9 AND NOT #8.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714