| Plan Review Notes For Permit 04010916 |
| Permit Number |
04010916 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-03 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE HAVE PLANS SIGNED, DATED | | | AND SEALED BY THE ARCH OF RECORD. PLANS | | | DO NOT CORRELATE WITH SIGNATURE ON | | | RECORD FOR ARCH. | | | PLEASE NOTE, ONE SET OF PLANS IS BEING | | | RETAINED FOR FILE FOR SAID VIOLATION. | | | PER FS 481.221 | | | | | | 2)NOTE: PLANS ARE REQUIRED TO HAVE ALL | | | LICENSE #'S ON TITLE BLOCK FOR ARCH/ | | | ARCH FIRM. INCLUDING NAME OF ARCH. | | | FAC 61G1-16.004 | | | | | | 3)NOTE: PLEASE SEE REQUIRMENT SHOWN FOR | | | ARC FAULT PROTECTION. SHOWS WHAT WAS | | | REQ'D UNDER THE 99 NEC. WE ARE NOW UNDER | | | THE 2002 CODE. PLEASE ADJUST | | | | | | 4)NOTE; PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEM MAIN DISC | | | AND PANEL. PER250.110,250.24 AND SIZE | | | PER 250.122 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|