Plan Review Notes
Plan Review Notes For Permit 04010913
Permit Number 04010913
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-30 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} AN EQUIPMENT GROUNDING CONDUCTOR IS
 REQUIRED FROM THE DISCONNECT TO THE
 PANEL PER 250.122.
  
 2} THE RECEPTACLE PLACEMENT IN THE
 MASTER BATH DOES NOT COMPLY WITH THE 3'
 REQUIREMENT OF ARTICLE 210.52(D).
  
 3} A SMOKE DETECTOR MUST BE ADDED
 OUTSIDE THE DOORS TO THE MASTER SUITE
 TO COMPLY WITH 8-1.4.1.6.2. NFPA-72.
  
 4} A SMOKE DETECTOR MUST BE ADDED
 OUTSIDE THE DOOR OF THE "DEN/BEDROOM
 3", ALSO FOR COMPLIANCE WITH
 8-1.4.1.6.2. NFPA-72.
  
 5} ANOTHER RECEPTACLE IS REQUIRED IN
 BATH #2 TO COMPLY WITH 210.52(D).
  
 6} NOTE THAT THE ARCHITECTS
 SIGNATURE IS REQUIRED ON HIS/HER SEAL
 PER 61G116.003.INITIALS ARE NOT
 ACCEPTABLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 2)NOTE: PLEASE SEE BLDG PLAN REVIEW
 NOTES. PLEASE CORRELATE PLANS/PAPERWORK
 FOR COTTAGES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 2)NOTE: PLEASE SEE BLDG PLAN REVIEW
 NOTES. PLEASE CORRELATE PLANS/PAPERWORK
 FOR COTTAGES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]