Text |
| 2004-01-30 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} AN EQUIPMENT GROUNDING CONDUCTOR IS |
| | REQUIRED FROM THE DISCONNECT TO THE |
| | PANEL PER 250.122. |
| | |
| | 2} THE RECEPTACLE PLACEMENT IN THE |
| | MASTER BATH DOES NOT COMPLY WITH THE 3' |
| | REQUIREMENT OF ARTICLE 210.52(D). |
| | |
| | 3} A SMOKE DETECTOR MUST BE ADDED |
| | OUTSIDE THE DOORS TO THE MASTER SUITE |
| | TO COMPLY WITH 8-1.4.1.6.2. NFPA-72. |
| | |
| | 4} A SMOKE DETECTOR MUST BE ADDED |
| | OUTSIDE THE DOOR OF THE "DEN/BEDROOM |
| | 3", ALSO FOR COMPLIANCE WITH |
| | 8-1.4.1.6.2. NFPA-72. |
| | |
| | 5} ANOTHER RECEPTACLE IS REQUIRED IN |
| | BATH #2 TO COMPLY WITH 210.52(D). |
| | |
| | 6} NOTE THAT THE ARCHITECTS |
| | SIGNATURE IS REQUIRED ON HIS/HER SEAL |
| | PER 61G116.003.INITIALS ARE NOT |
| | ACCEPTABLE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | 2)NOTE: PLEASE SEE BLDG PLAN REVIEW |
| | NOTES. PLEASE CORRELATE PLANS/PAPERWORK |
| | FOR COTTAGES. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | 2)NOTE: PLEASE SEE BLDG PLAN REVIEW |
| | NOTES. PLEASE CORRELATE PLANS/PAPERWORK |
| | FOR COTTAGES. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |