| Plan Review Notes For Permit 04010911 |
| Permit Number |
04010911 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-28 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE NOTE THAT THE ARCHITECTS | | | SIGNATURE IS REQUIRED ON HIS/HER | | | SEAL.61G1-16.003.INITIALS ARE NOT | | | ACCEPTABLE. | | | | | | 2} THE METER LOCATION ON THE PLAN DOES | | | NOT SHOW A DISONNECT, BUT THE RISER | | | DOES , PLEASE CORRELATE. | | | | | | 3} THERE MUST AN EQUIPMENT GROUND RAN | | | WITH THE FEEDER FROM THE DISCONNECT (IF | | | THERE IS ONE INSTALLED) TO THE PANEL | | | PER250.122. | | | | | | 4} IN BEDROOM #3 THERE MUST BE A | | | RECEPTACLE ADDED AT THE ENTRANCE PER | | | 210.52(A)(2). | | | | | | 5} TO COMPLY WITH 905.2.2 F.B.C. A | | | SMOKEDETECTOR MUST BE INSTALLED OUTSIDE | | | THE HALL LEADING TO THE MASTER SUITE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|