Plan Review Notes
Plan Review Notes For Permit 04010911
Permit Number 04010911
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-28 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE NOTE THAT THE ARCHITECTS
 SIGNATURE IS REQUIRED ON HIS/HER
 SEAL.61G1-16.003.INITIALS ARE NOT
 ACCEPTABLE.
  
 2} THE METER LOCATION ON THE PLAN DOES
 NOT SHOW A DISONNECT, BUT THE RISER
 DOES , PLEASE CORRELATE.
  
 3} THERE MUST AN EQUIPMENT GROUND RAN
 WITH THE FEEDER FROM THE DISCONNECT (IF
 THERE IS ONE INSTALLED) TO THE PANEL
 PER250.122.
  
 4} IN BEDROOM #3 THERE MUST BE A
 RECEPTACLE ADDED AT THE ENTRANCE PER
 210.52(A)(2).
  
 5} TO COMPLY WITH 905.2.2 F.B.C. A
 SMOKEDETECTOR MUST BE INSTALLED OUTSIDE
 THE HALL LEADING TO THE MASTER SUITE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved