| 2004-03-02 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04010909 |
| | ADD: 4847 FRED GLADSTONE DR |
| | CONT: THE WHITING-TURNER |
| | TEL: (561)718-2367 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | WHERE THE BEARING CAPACITY OF THE SOIL I |
| | S NOT DEFINITEY KNOWN, OR IS IN QUESTION |
| | THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| | ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| | TO THE PERMISSIBLE SAFE BEARING |
| | CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| | TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| | CITY SHALL BE CERTIFIED BY A GEOTECH- |
| | NICALREPORT FROM A DESIGN PROFESSIONAL P |
| | ROPERLY LICENSED IN THE STATE OF |
| | FLORIDA. |
| | |
| | 3) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS FIXED OR SLIDERS |
| | B) SWING EXTERIOR DOORS |
| | C) ROOFING ASSEMBLIES |
| | D) STORM SHUTTERS |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 4) PROVIDE THE SCREW SIZE AND SPACING |
| | FOR THE WALL AND ROOF SHEATHING? |
| | |
| | 5) 2304.5 CLEARENCE BETWEEN WOOD SIDING |
| | & EARTH ON THE EXTERIOR OF A BUILDING |
| | SHALL NOT BE LESS THAN 6" EXCEPT WHERE |
| | SIDING, SHEATHING AND FRAME WALL ARE OF |
| | APPROVED DURABLE WOOD OR APPROVED PRE- |
| | SERVATIVE TREAATED WOOD. |
| | |
| | 6) PROVIDE ADD INFORMATION AS TO GUAGE |
| | OF EXTERIOR WALL STUDS? |
| | |
| | 7) PROVIDE WINDOW AND DOOR BUCK DETAILS |
| | AND ATTACHMENT SCHEDULE? |
| | |
| | 8)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |