| Plan Review Notes For Permit 04010887 |
| Permit Number |
04010887 |
|
| Review Stop |
P |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2004-08-18 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | | | | 1) SHTS P7 & P8 HUB DRAIN NOT APPROVED | | | FOR INDIRECT WASTE FOR DISHWASHER. HUB | | | DRAINS ARE APPROVED FOR CLEAR WASTE ONLY | | | AND A FLOOR SINK IS REQUIRED FOR THE | | | DISCHARGE FROM A DISHWASHER. SECTION | | | 802.3 | | | 2) FROM PREVIOUS REVIEW: SHT P8 WATER | | | ISOMETRIC, WATER HAMMER ARRESTORS SHALL | | | BE LOCATED IN AN "EFFECTIVE RANGE" NOT | | | IN THE CEILING AS SHOWN. PDI-WH 201 AND | | | MANUF. INSTALLATION INSTRUCTIONS WHICH | | | FROM THE INFORMATION SUBMITTED STATES, | | | "AS CLOSE TO THE VALVE(S) AS POSSIBLE. | | | RESPONSE NOTED, BUT NOT APPROVED. | | | 3) EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. FROM PRE- | | | VIOUS REVIEW: RESPONSE NOTED, BUT NOT | | | APPROVED. | | | 4) SHUT OFF VALVES TO GAS APPLIANCES | | | SHALL BE FULL SIZE AS THE PIPE REQUIRED | | | TO SUPPLY THE APPLIANCE. SEE RED LINE | | | CORRECTIONS FOR SHUT OFF VALVE SIZE. | | | MAKE CORRECTIONS AND RESUBMIT PLANS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|