Plan Review Notes
Plan Review Notes For Permit 04010887
Permit Number 04010887
Review Stop P
Sequence Number 6
Notes
Date Text
2004-08-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SHTS P7 & P8 HUB DRAIN NOT APPROVED
 FOR INDIRECT WASTE FOR DISHWASHER. HUB
 DRAINS ARE APPROVED FOR CLEAR WASTE ONLY
 AND A FLOOR SINK IS REQUIRED FOR THE
 DISCHARGE FROM A DISHWASHER. SECTION
 802.3
 2) FROM PREVIOUS REVIEW: SHT P8 WATER
 ISOMETRIC, WATER HAMMER ARRESTORS SHALL
 BE LOCATED IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS WHICH
 FROM THE INFORMATION SUBMITTED STATES,
 "AS CLOSE TO THE VALVE(S) AS POSSIBLE.
 RESPONSE NOTED, BUT NOT APPROVED.
 3) EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. FROM PRE-
 VIOUS REVIEW: RESPONSE NOTED, BUT NOT
 APPROVED.
 4) SHUT OFF VALVES TO GAS APPLIANCES
 SHALL BE FULL SIZE AS THE PIPE REQUIRED
 TO SUPPLY THE APPLIANCE. SEE RED LINE
 CORRECTIONS FOR SHUT OFF VALVE SIZE.
 MAKE CORRECTIONS AND RESUBMIT PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]