Plan Review Notes
Plan Review Notes For Permit 04010887
Permit Number 04010887
Review Stop P
Sequence Number 5
Notes
Date Text
2004-07-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 CITY CODE
  
 1) SHT P-2 NO REVISION #3 FOUND. PLEASE
 CLARIFY.
 2) SHT P-3 NO REVISION #3 FOUND. PLEASE
 CLARIFY.
 3) SHT P-7 DEMO'D PIPES SHALL BE INSPTE-
 TED PRIOR TO COVERING. - ALSO IN THE IN-
 STALLATION OR REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE PRO-
 HIBITED. SECTION 704.5
 4) SHT P-7 DISH WASHERS SHALL BE CONNEC-
 TED TO SANITARY SYSTEM, NOT GREASE SYST-
 EM. CITY CODE.
 5) SHT P-8 WATER ISOMETRIC, WATER HAMMER
 ARRESTORS SHALL BE LOCATED IN AN "EFFEC-
 TIVE RANGE" NOT IN THE CEILING. PDI-WH
 201 AND MANUF. INSTALL. INSTRUCTIONS.
 6) THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT. SEPERATE GAS PER REQUIR-
 ED.
 A. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 B. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 C. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 E. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  