| Date |
Text |
| 2004-07-27 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | CITY CODE |
| | |
| | 1) SHT P-2 NO REVISION #3 FOUND. PLEASE |
| | CLARIFY. |
| | 2) SHT P-3 NO REVISION #3 FOUND. PLEASE |
| | CLARIFY. |
| | 3) SHT P-7 DEMO'D PIPES SHALL BE INSPTE- |
| | TED PRIOR TO COVERING. - ALSO IN THE IN- |
| | STALLATION OR REMOVAL OF ANY PART OF A |
| | DRAINAGE SYSTEM, DEAD ENDS SHALL BE PRO- |
| | HIBITED. SECTION 704.5 |
| | 4) SHT P-7 DISH WASHERS SHALL BE CONNEC- |
| | TED TO SANITARY SYSTEM, NOT GREASE SYST- |
| | EM. CITY CODE. |
| | 5) SHT P-8 WATER ISOMETRIC, WATER HAMMER |
| | ARRESTORS SHALL BE LOCATED IN AN "EFFEC- |
| | TIVE RANGE" NOT IN THE CEILING. PDI-WH |
| | 201 AND MANUF. INSTALL. INSTRUCTIONS. |
| | 6) THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR GAS PERMIT. SEPERATE GAS PER REQUIR- |
| | ED. |
| | A. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | B. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | C. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | E. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | REVIEW BY KEN STEVENS |