Plan Review Notes
Plan Review Notes For Permit 04010887
Permit Number 04010887
Review Stop P
Sequence Number 2
Notes
Date Text
2004-03-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 ADA ACCESSIBILITY GUIDELINES
 BLDG. ELEMENTS DESIGNED FOR
 CHILDREN'S USE
  
 A) COMMENTS FROM PREVIOUS REVIEW HAVE
 NOT BEEN RESPONDED TO SUFFICIENTLY. THE
 NUMBER OF THE COMMENT SHALL STAY THE
 SAME AS ORIGINAL REVIEW TO PREVENT CON-
 FUSION.
 1) SHT A1 SECTION 11-4.1(6) IF TOILET
 FACILITIES ARE PROVIDED ON A SITE, THEN
 EACH SUCH PUBLIC OR COMMON USE TOILET
 FACILITIY SHALL COMPLY WITH 11-4.22.
 TOILET ROOMS 116, 120, 124, AND 147
 SHALL COMPLY WITH 11-4.16, 11-4.18, AND
 11-4.22 AND ALL SUBSECTIONS. SUBMIT A
 DETAIL SHOWING COMPLIANCE. - RESPONSE
 NOTED. BUILDING OFFICIAL STATED THAT ALL
 TOILET ROOMS SHALL COMPLY WITH ADA GUID-
 LINES FOR BUILDING ELEMENTS DESIGNED FOR
 CHILDREN'S USE. 4.16.7(2) RECOMMENDS W/C
 SEAT HEIGHT BE 12" FOR AGES 3 AND 4, BUT
 ATTACHED SHEET SHOWS 10". 4.16.7 RECOMM-
 ENDS CENTERLINE OF W/C TO BE 12" OFF THE
 WALL. SECTION 4.16(7) RECOMMENDS A GRAB
 BAR HEIGHT BETWEEN 18" & 20". ATTACHED
 SHEET SHOWS 22" AND NOT GRAB BARS ARE
 SHOWN IN TOILET ROOMS MENTIONED ABOVE.
 FLUSH CONTROLS SHALL BE A MAXIMUM HEIGHT
 OF 36" FOR W/C'S SERVING CHILDREN AGES
 2 TO 4. 4.16.7(5) TOILET PAPER DISPENS-
 ERS TO BE 14" TO 19".
 2) PLANS SHALL BE ROUTED TO THE PALM
 BEACH COUNTY HEALTH UNIT DIVISION OF
 ENVIRONMENTAL HEALTH, 901 EVERNIA STREET
 WPB 33401. (561) 355-3018 PRIOR TO RE-
 SUBMITTING TO CITY OF WPB FOR REVIEW.
 SECTION 101.4.7. - RESPONSE NOTED, BUT
 NO STAMP FROM THE HEALTH DEPT. WAS FOUND
 ON SHEET A-1.
 3) SHT A4 ACCESSIBLE TOILET DETAILS.
 SUBMIT INFORMATION ON TA-6 TOILET PAPER
 DISPENSER SHOWING ADA APPROVAL. PAPER
 DISPENSER IS ENCHROACHING INTO THE CLEAR
 FLOOR SPACE FOR W/C. 11-4.18.2 - RESPON-
 SE NOTED, BUT NO CUT SHEETS WERE FOUND.
 11) EACH WATER CLOSET UTILIZED BY THE
 PUBLIC OR EMPLOYEES SHALL OCCUPY A SEP-
 ARATE COMPARTMENT WITH A DOOR AND WALLS
 OR PARTITIONS BETWEEN FIXTURES TO EN-
 SURE PRIVACY. SECTION 310.4 - RESPONSE
 NOTED. IS ARTICLE X PHYSICAL FACILITIES,
 E) TOILET AND BATH FACILITIES, P.37 AN
 EXEMPTION TO THE CODE? PLEASE PROVIDE
 THIS INFORMATION.
 12) WATER CLOSET COMPARTMENTS SHALL NOT
 BE LESS THAN 30" WIDE AND 60" DEEP. -
 RESPONSE NOTED.SEE COMMENT #11.
  
 REVIEW BY KEN STEVENS