| Plan Review Notes For Permit 04010887 |
| Permit Number |
04010887 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-03-29 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)TO EXPEDITE PLAN REVIEW, ALL | | | CHANGES TO THE PLAN ARE TO BE CLEARLY | | | MARKED.FOR INSTANCE, SHEET LS1, THE | | | ROOM DESIGNATIONS WERE CHANGED FROM | | | "CLASSROOM" TO "ROOM".THIS WAS DONE ON | | | SEVERAL SHEETS, BUT NONE WERE MARKED. | | | | | | 2.)NOTE:DAYCARE (D) OCCUPANCY AS | | | PER LETTER FROM ALLAN DEUPP, MANAGER, | | | PROCUREMENT & PROJECT IMPLEMENTATION | | | GROUP, PALM BEACH COUNTY. | | | | | | 3.)FBC423.21.4, TOILET FACILITIES | | | SHALL HAVE A 6' IMPERVIOUS WAINSCOT. | | | | | | 4.)PROVIDE TEST REPORTS AND FLORIDA | | | STATEWIDE, LOCAL OR SITE SPECIFIC | | | PRODUCT APPROVALS FOR THE EXTERIOR DOORS | | | AND STOREFRONT GLASS. | | | WWW.FLORIDABUILDING.ORG. | | | | | | 5.)THE PRINTED NAME AND LICENSE | | | NUMBER OF THE PERSON SEALING THE PLAN | | | IS TO BE PRINTED ON EACH SHEET, FAC | | | 61G1-16.003.THE SEAL ON SOME SHEETS | | | IS ILLEGIBLE. |
|