Plan Review Notes
Plan Review Notes For Permit 04010887
Permit Number 04010887
Review Stop P
Sequence Number 1
Notes
Date Text
2004-02-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTPER 1
 FBC-2001 CHAPTER 11
 ADA ACCESSIBILITY GUIDELINES
 FOR BLDGS AND FACILITIES;
 BUILDING ELEMENTS DESIGN-
 ED FOR CHILDRES'S USE
  
 1) SHT A1 SECTION 11-4.1(6) IF TOILET
 FACILITIES ARE PROVIDED ON A SITE, THEN
 EACH SUCH PUBLIC OR COMMON USE TOILET
 FACILITY SHALL COMPLY WITH 11-4.22.
 TOILET ROOMS 116, 120, 124, AND 147
 SHALL COMPLY WITH 11-4.16, 11-4.18, AND
 11-4.22 AND ALL SUBSECTIONS. SUBMIT A
 DETAIL SHOWING COMPLIANCE.
 2) PLANS SHALL BE ROUTED TO THE PALM
 BEACH COUNTY HEALTH UNIT DIVISION OF
 ENVIRONMENTAL HEALTH, 901 EVERNIA STREET
 WPB 33401. (561) 355-3018 PRIOR TO RE-
 SUBMITTING TO CITY OF WPB FOR REVIEW.
 SECTION 101.4.7
 3) SHT A4 ACCESSIBLE TOILET DETAILS.
 SUBMIT INFORMATION ON TA-6 TOILET PAPER
 DISPENSER SHOWING ADA APPROVAL. PAPER
 DISPENSER IS ENCHOACHING INTO CLEAR
 FLOOR SPACE FOR W/C. 11-4.16.2
 4) SHT A4 DETAIL 1/A4(B) SHOW URNAL
 HEIGHT FOR URINAL PER 11-4.18.2.
 5) SHT A4 SHOW CLEAR FLOOR SPACE FOR
 URINAL ON PLAN ENLARGMENT PER SECTION
 11-4.18.3.
 6) SUBMIT CALCULATIONS FOR MINIMUM FIX-
 TURES, (FACILITIES), PER TABLE 403.1 IN
 PLUMBING AND TABLE 1003.1 IN BUILDING.
 7) SHT P-1 DEMO NOTES: ALL CAPPED PLUMB-
 ING LINES SHALL BE INSPECTED PRIOR TO
 COVERING.
 8) SHT P-1 PLUMBING SPECIFICATIONS #4(B)
 DIELECTRIC UNIONS ARE NOT APPROVED FOR
 WATER USE. DELET FROM REFERENCE.
 9) SHT P-5 WATER ISOMETRIC AT TOILET
 ROOMS 124, 120 & PUBLIC RESTROOMS. WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS. 604.9
 (ALSO SEE #137 IN CORRIDOR).
 10) SHT P-6 FLOOR MOUNTED ELECTRIC WATER
 HEATER DETAIL. THERMAL EXPANSION CONTROL
 REQUIRED PER SECTION 607.3.2. PROVIDE A
 DETAIL.
 11) EACH WATER CLOSET UTILIZED BY THE
 PUBLIC OR EMPLOYEES SHALL OCCUPY A SEP-
 ARATE COMPARTMENT WITH A DOOR AND WALLS
 OR PARTITIONS BETWEEN DIXTURES TO EN-
 SURE PRIVACY. SECTION 310.4
 12) WATER COLSET COMPARTMENTS SHALL NOT
 BE LESS THAN 30" WIDE AND 60" DEEP.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]