| Plan Review Notes For Permit 04010887 |
| Permit Number |
04010887 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-26 00:00:00 | PLAN REVIEW ONLY, NOT A PERMIT | | | APPLICATION. | | | | | | SHEET LS1 DECLARES BUILDING TYPE AS "IV | | | UNPROTECTED 1 HOUR SPRINKLERED."PLEASE | | | CLARIFY. | | | | | | SHEET LS1 DECLARES OCCUPANCY AS DAY | | | CARE.IT APPEARS THE INTENDED OCCUPANCY | | | IS PRIMARILY PRE-SCHOOL, IE; | | | EDUCATIONAL.SEE FBC 313.1. | | | | | | FBC TABLE 704.1 REQUIRES A 2 HR FIRE | | | RATED MIXED OCCUPANCY SEPARATION FOR | | | GROUP E OCCUPANCY.PLEASE REVISE AS | | | NECESSARY. | | | | | | SHEET A2, DETAILS 1/A2, 2/A2 AND 3/A2. | | | SHOW SPECIFIC CONNECTION METHODS FOR THE | | | FRAMING TO THE EXISTING STRUCTURE.SEE | | | FBC 104.2.1. |
|