2004-06-15 00:00:00REVISION CHECKLIST:
 1-PROVIDE COMPLETE INFORMATION FOR PRE-
 FABRICATED MASONRY FIREPLACE TO BE
 USED OUTDOORS AS REQUIRED BY SECTION
 2806 FBC 2001. (PROVIDE LISTING AND
 COMPLETE SPECS/INSTALLATION PACKAGE)
 **ARCHITECT TO REVIEW AND APPROVE PRE-
 FABRICATED FIREPLACE PACKAGE PRIOR TO
 SUBMITTAL TO THIS OFFICE.
 2-PROVIDE COMPLETE SECTION DETAIL TRU
 FIREPLACE AND CHIMNEY THAT REFLECTS
 ACTUAL FIELD CONDITIONS. REVISE ROOF
 FRAMING PLAN TO SHOW CHIMNEY AND FLUE
 LOCATION TO VERIFY FOR CLEARANCES
 (AS REQUIRED BY THE FLUE LISTING AND
 SPECIFICATIONS) SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 3-SPECIFY AND SHOW LOCATION OF FIRE-
 BLOCKING AS REQUIRED BY SEC. 2305.1.3
 AND 2305.1.4 FBC 2001.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.