| 2004-03-09 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-PAY IMPACT FEES. BRING BACK STAMPED |
| | DRAWINGS AND PAID RECEIPT. |
| | 2-NOTICE OF COMMENCEMENT IS VOID. NO |
| | WORK WITHING 90 DAYS OF RECORDATION. |
| | 3-DESIGN CRITERIA: NEED TO ADD 30PSF OR |
| | 10PSF ATTIC LIVE LOAD AS REQUIRED BY |
| | TABLE 1604.1 FBC 2001. THESE LOADS |
| | NEED TO BE SPECIFIED FOR ATTIC AREA |
| | (BOTTOM CHORD OF TRUSS). INFORMATION |
| | GIVEN ON SHEET A-9 DOESN'T ADDRESS THE |
| | ATTIC AREA, BUT ROOF LIVE LOAD ONLY. |
| | 4-NEED COMPLETE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL INFORMATION FOR BUTT GLAZING |
| | SYSTEM TO BE USED. USE UPDATED FORM& |
| | PROVIDE ALL INFO. REQUESTED ON IT. |
| | **NOTE: ENGINEER TO PROVIDE ALL INFO. AS |
| | AS REQUESTED ON RULE 9B-72 SECTION |
| | 9B-72.040(5). SEE ATTACHED COPY. ALSO, |
| | SEE WWW.FLORIDABUILDING.ORG. |
| | 5-PROVIDE FLORIDA/LOCAL PRODUCT APPROVAL |
| | FOR FRENCH DOORS WITH TRANSOM ABOVE |
| | UNIT AS SHOWN ON PLANS. |
| | 6-PROVIDE FLORIDA/LOCAL PRODUCT APPROVAL |
| | FOR SLIDING GLASS DOORS WITH TRANSOM |
| | ABOVE SINGLE UNIT AS SHOWN ON PLANS. |
| | 7-CLARIFY WHERE ARE TRUSSES RESTING AT |
| | ENTRY PORCH ROOF. ONE SIDE WAS CLARI- |
| | FIED BUT THE OTHER SIDE DOESN'T SHOW |
| | A GIRDER BELOW. SEE COMMENTS ON PLANS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 8-OWES $628.11 FOR LOW VALUE DECLARED |
| | ON APPLICATION AND RADON FEES. |
| | 9-SUBMIT FLORIDA OR LOCAL PRODUCT APPROV |
| | AL FOR ALL DOORS & WINDOWS TO BE INSTA |
| | LLED IN THIS HOUSE TO AVOID CONFUSION |
| | AND EXPEDITE THE REVIEW PROCESS. |
| | **CLEARLY IDENTIFY WHEN USING IMPACT GLA |
| | ZING PRODUCTS. |
| | 10-CLARIFY IF PROVIDING STORM SHUTTERS |
| | OR MISSILE IMPACT GLAZING ON DOORS AND |
| | WINDOWS. BOTH PACKAGES WERE SUBMITTED |
| | AND IS UNCLEAR WHAT AREAS ARE TO BE |
| | PROTECTED WITH SHUTTERS OR NOT SINCE |
| | SHUTTERS INSTALLATION SCHEDULE COVERS |
| | ALL OPENINGS. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 11-IF USING STORM SHUTTERS: A)PROVIDE |
| | KEY PLAN & INSTALLATION SCHEDULE THAT |
| | MATCHES FLOOR PLAN. |
| | B)NEED APPROVED FLORIDA PRODUCT APPROVAL |
| | AND DRAWINGS THAT MATCH SUCH APPROVAL. |
| | C)REVISE THE "PEAK ROOF HEIGHT" SHOWN ON |
| | SUBMITTED DRAWINGS. SEE HOW THE PEAK |
| | ROOF HEIGHT IS MEASURED AND REVISE IT. |
| | D)PROVIDE LEGIBLE DRAWINGS. |
| | E)CHECK DRAWINGS FOR PANEL LIMITATIONS. |
| | F)CLEARLY INDICATE THE EGRESS OPENING AS |
| | REQUIRED BY SEC. 1005.4.5 FBC 2001. |
| | G)CLEARLY INDICATE MOUNTING CONDITIONS |
| | AND ANCHOR TYPE AND SPACING TO BE USED |
| | ACCORDING TO THE DESIGN PRESSURES,EDGE |
| | DISTANCE, PANEL SPAN, CONNECTION TYPE |
| | AND STRUCTURE TO BE ATTACHED TO (MASON |
| | RY OR CONCRETE). |
| | 12-NEED FLORIDA/LOCAL PRODUCT APPROVAL |
| | FOR GARAGE DOOR (LARGER DOOR). |
| | 13-CLARIFY IF ENTRY DOORS ARE IMPACT OR |
| | NOT IMPACT. NEED TO CHECK FOR EGRESS. |
| | SEC. 1026 FBC 2001. |
| | 14-NEED FL. OR LOCAL PRODUCT APPROVAL |
| | FOR ROOF TILE. |
| | 15-PROVIDE APPROVED FLORIDA OR APPLY FOR |
| | LOCAL PRODUCT APPROVAL FOR GLASS BLOCK |
| | 16-PROVIDE PRODUCT APPROVAL FOR FIXED |
| | WINDOWS WITH SIZES AS SHOWN ON PLANS. |
| | 17-NEED FL. OR LOCAL PRODUCT APPROVAL |
| | FOR WINDOW MULLIONS. |
| | **CLEARLY MARK ON DWGS SPECIFIC MULLION |
| | SIZE AND COMPONENTS TO BE USED. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 18-NEED FL. OR LOCAL PRODUCT APPROVAL |
| | FOR ALL STRUCTURAL CONNECTORS. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL |
| | JULIO GOMEZ AT 805-6712. |