Plan Review Notes
Plan Review Notes For Permit 04010875
Permit Number 04010875
Review Stop B
Sequence Number 2
Notes
Date Text
2004-03-09 00:00:00BUILDING REVIEW CHECKLIST:
 1-PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 2-NOTICE OF COMMENCEMENT IS VOID. NO
 WORK WITHING 90 DAYS OF RECORDATION.
 3-DESIGN CRITERIA: NEED TO ADD 30PSF OR
 10PSF ATTIC LIVE LOAD AS REQUIRED BY
 TABLE 1604.1 FBC 2001. THESE LOADS
 NEED TO BE SPECIFIED FOR ATTIC AREA
 (BOTTOM CHORD OF TRUSS). INFORMATION
 GIVEN ON SHEET A-9 DOESN'T ADDRESS THE
 ATTIC AREA, BUT ROOF LIVE LOAD ONLY.
 4-NEED COMPLETE FLORIDA OR LOCAL PRODUCT
 APPROVAL INFORMATION FOR BUTT GLAZING
 SYSTEM TO BE USED. USE UPDATED FORM&
 PROVIDE ALL INFO. REQUESTED ON IT.
 **NOTE: ENGINEER TO PROVIDE ALL INFO. AS
 AS REQUESTED ON RULE 9B-72 SECTION
 9B-72.040(5). SEE ATTACHED COPY. ALSO,
 SEE WWW.FLORIDABUILDING.ORG.
 5-PROVIDE FLORIDA/LOCAL PRODUCT APPROVAL
 FOR FRENCH DOORS WITH TRANSOM ABOVE
 UNIT AS SHOWN ON PLANS.
 6-PROVIDE FLORIDA/LOCAL PRODUCT APPROVAL
 FOR SLIDING GLASS DOORS WITH TRANSOM
 ABOVE SINGLE UNIT AS SHOWN ON PLANS.
 7-CLARIFY WHERE ARE TRUSSES RESTING AT
 ENTRY PORCH ROOF. ONE SIDE WAS CLARI-
 FIED BUT THE OTHER SIDE DOESN'T SHOW
 A GIRDER BELOW. SEE COMMENTS ON PLANS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-OWES $628.11 FOR LOW VALUE DECLARED
 ON APPLICATION AND RADON FEES.
 9-SUBMIT FLORIDA OR LOCAL PRODUCT APPROV
 AL FOR ALL DOORS & WINDOWS TO BE INSTA
 LLED IN THIS HOUSE TO AVOID CONFUSION
 AND EXPEDITE THE REVIEW PROCESS.
 **CLEARLY IDENTIFY WHEN USING IMPACT GLA
 ZING PRODUCTS.
 10-CLARIFY IF PROVIDING STORM SHUTTERS
 OR MISSILE IMPACT GLAZING ON DOORS AND
 WINDOWS. BOTH PACKAGES WERE SUBMITTED
 AND IS UNCLEAR WHAT AREAS ARE TO BE
 PROTECTED WITH SHUTTERS OR NOT SINCE
 SHUTTERS INSTALLATION SCHEDULE COVERS
 ALL OPENINGS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 11-IF USING STORM SHUTTERS: A)PROVIDE
 KEY PLAN & INSTALLATION SCHEDULE THAT
 MATCHES FLOOR PLAN.
 B)NEED APPROVED FLORIDA PRODUCT APPROVAL
 AND DRAWINGS THAT MATCH SUCH APPROVAL.
 C)REVISE THE "PEAK ROOF HEIGHT" SHOWN ON
 SUBMITTED DRAWINGS. SEE HOW THE PEAK
 ROOF HEIGHT IS MEASURED AND REVISE IT.
 D)PROVIDE LEGIBLE DRAWINGS.
 E)CHECK DRAWINGS FOR PANEL LIMITATIONS.
 F)CLEARLY INDICATE THE EGRESS OPENING AS
 REQUIRED BY SEC. 1005.4.5 FBC 2001.
 G)CLEARLY INDICATE MOUNTING CONDITIONS
 AND ANCHOR TYPE AND SPACING TO BE USED
 ACCORDING TO THE DESIGN PRESSURES,EDGE
 DISTANCE, PANEL SPAN, CONNECTION TYPE
 AND STRUCTURE TO BE ATTACHED TO (MASON
 RY OR CONCRETE).
 12-NEED FLORIDA/LOCAL PRODUCT APPROVAL
 FOR GARAGE DOOR (LARGER DOOR).
 13-CLARIFY IF ENTRY DOORS ARE IMPACT OR
 NOT IMPACT. NEED TO CHECK FOR EGRESS.
 SEC. 1026 FBC 2001.
 14-NEED FL. OR LOCAL PRODUCT APPROVAL
 FOR ROOF TILE.
 15-PROVIDE APPROVED FLORIDA OR APPLY FOR
 LOCAL PRODUCT APPROVAL FOR GLASS BLOCK
 16-PROVIDE PRODUCT APPROVAL FOR FIXED
 WINDOWS WITH SIZES AS SHOWN ON PLANS.
 17-NEED FL. OR LOCAL PRODUCT APPROVAL
 FOR WINDOW MULLIONS.
 **CLEARLY MARK ON DWGS SPECIFIC MULLION
 SIZE AND COMPONENTS TO BE USED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 18-NEED FL. OR LOCAL PRODUCT APPROVAL
 FOR ALL STRUCTURAL CONNECTORS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 JULIO GOMEZ AT 805-6712.