Plan Review Notes
Plan Review Notes For Permit 04010875
Permit Number 04010875
Review Stop B
Sequence Number 1
Notes
Date Text
2004-02-18 00:00:00BUILDING REVIEW CHECKLIST:
 1-PAY IMPACT FEES BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 2-DESIGN CRITERIA: NEED TO ADD 30PSF OR
 10PSF ATTIC LIVE LOAD ACCORDING TO FBC
 2001 TABLE 1604.1.
 3-ENGINEER TO SIGN, SEAL DWGS AS REQ'D
 BY CHAPTER 471 FLORIDA STATUTES.
 4-DESIGN JOINTS OR SPECIFY WWM SUPPORTS
 AND SPACING ON CONCRETE SLAB AS REQ'D
 SEC. 1909.3 FBC 2001.
 5-SPECIFY SIZE OF ATTIC ACCESS. SECTION
 2309.6 FBC 2001.
 6-NEED COMPLETE BATHROOM WITH DOORS THAT
 ALLOWS 29" MIN. CLEAR OPENING AS REQ'D
 BY SEC. 11-11 FBC 2001.
 7-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR BUTT GLAZING SYSTEMS USED
 8-PROVIDE PRODUCT APPROVAL FOR FRENCH
 DOORS W/ TRANSOM ABOVE SINGLE ASSEMBLY
 AS SHOWN ON PLANS.
 9-PROVIDE PRODUCT APPROVAL FOR SLIDING
 GLASS DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 10-PROVIDE DETAIL/SPECS FOR CEILING
 INSTALLATION AT ENTRY & REAR PORCHES.
 SEE ASTM C-926 AND ASTM C-1063.
 SEC. 2504.2 FBC 2001.
 11-PROVIDE DETAILS FOR CONSTRUCTION/
 INSTALLATION OF BEAM BOX OUT AT REAR
 PORCHES. SEC. 104.2.1.2 CITY AMENDMENT
 TO FBC 2001.
 12-PROVIDE COMPLETE DETAIL/SECTION FOR
 INSTALLATION OF HANGING AIR HANDLING
 UNITS. SPECIFY ALL FASTENERS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 13-UPDATE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001, WHICH DOESN'T ALLOW
 THE STEEL STRESS TO BE INCREASED.
 PROVIDE ENGINEERING FOR UPLIFT AND
 FASTENERS THAT DIFFER FROM THOSE THAT
 WERE TESTED AND PUBLISHED BY USP.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 14-SHEET A-5: A)REVISE ROOF LAYOUT
 SHOWING ROOF ZONES. SEE ASCE 7-98
 FIGURE 6-5B.
 B)THERE ARE SOME CONNECTORS THAT DON'T
 RESIST THE LOADS CALCULATED ON THE
 ROOF FRAMING PLAN. SEE PLANS FOR
 COMMENTS AND REVISE AS REQUIRED.
 C)CLARIFY WHERE ARE TRUSSES RESTING AT
 ENTRY PORCH. SEE PLAN FOR COMMENTS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 15-CLARIFY WHAT ARE DETAILS ON DWG A-10
 FOR?. WHERE ARE THEY APPLIED IN THIS
 PROJECT. SEC. 104.2.1.2 CITY AMENDMENT
 16-PROVIDE 2 COPIES SIGNED AND SEALED.
 ONLY ONE WAS SUBMITTED.
 17-OWES $628.11 FOR DECLARED LOW VALUE
 AND RADON FEES.
 18-ONLY PROVIDE PRODUCT APPROVAL FOR
 ITEMS THAT ARE USED IN THIS PROJECT.
 19-CLARIFY IF PROVIDING STORM SHUTTERS
 OR MISSILE IMPACT GLAZONG ON DOORS AND
 WINDOWS. BOTH PACKAGES WERE SUBMITTED
 **IF USING STORM SHUTTERS, THEN, PROVIDE
 UPDATED KEY PLAN THAT MATCHES PLAN
 SUBMITTED. ALSO, NEED DWGS THAT MATCH
 FLORIDA PRODUCT APPROVAL AND THAT ARE
 LEGIBLE.
 **CLEARLY INDICATE THE REQUIRED MEANS OF
 ESCAPE REQ'D BY SEC. 1005.4.5 FBC 2001
 20-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR GARAGE DOORS. RULE 9B-72.
 21-PROVIDE LEGIBLE DRAWINGS FOR SWINGING
 EXTERIOR DOORS.
 22-CLARIFY WHERE IS THE "IMPACT WALL
 3000" ALUMINUM WINDOW GOING TO BE
 INSTALLED. PROVIDE FLORIDA OR LOCAL
 PRODUCT APPROVAL WITH LEGIBLE DRAWINGS
 23-WINDOW MULLION PRODUCT APPROVAL:
 A)NEED DRAWINGS THAT MATCH FLORIDA
 PRODUCT APPROVAL REPORT.
 B)CLEARLY MARK ON DRAWINGS THE SPECIFIC
 COMPONENTS TO BE USD IN THIS PROJECT.
 24-SITE PLAN ON SHEET A-4 SHOW WRONG
 ORIENTATION. REVISE NORTH ARROW.
 SEE SURVEY.
 25-WALL SECTIONS ON SHEET A-7: SHOW MIN.
 FINISH FLOOR ELEVATION IN RELATION TO
 THE GRADE. SEC. 1804.1.7 CITY
 AMENDMENTS TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.