| 2004-02-03 00:00:00 | ***** NOTES REDLINED. ********* | | | | | | 1)NOTE: PLEASE SEE FEEDERS AND SEC'S | | | SHOWN RATED FOR 200A'S NOT FOR THE 225A | | | SHOWN. PLEASE SEE 310.15B6 FOR MIN | | | AWG OF 3/0'S. | | | | | | PLEASE CORRECT PLANS ALONG WITH ANY | | | REVISIONS AND/OR OPTIONS BEFORE ROUGH. |
|