Plan Review Notes
Plan Review Notes For Permit 04010874
Permit Number 04010874
Review Stop B
Sequence Number 1
Notes
Date Text
2004-02-25 00:00:00BUILDING REVIEW CHECKLIST:
 1-PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 2-NORTH ARROW ORIENTATION SHOWN ON THE
 SITE PLAN IS INCORRECT. SEE SURVEY AND
 REVISE AS REQUIRED.
 3-ENERGY CALCULATIONS: A)ORIENTATION OF
 BUILDING DOESN'T MATCH PLANS. SEE
 SURVEY AND REVISE CALCULATIONS. OR DO
 WORST CASE SCENARIO.
 B)REVISE UNDER ATTIC AREA. SEE SECTION
 604.1.A.1 OF CHAPTER 13 FBC 2001.
 4-PROVIDE COMPLETE BATHROOM WITH A DOOR
 THAT ALLOWS 29" MIN. CLEAR OPENING.
 SEC. 11-11 FBC 2001.
 5-DESIGN CRITERIA: ADD THE 30PSF/10PSF
 ATTIC LIVE LOAD AS REQUIRED BY TABLE
 1604.1 FBC 2001.
 6-PROVIDE BBQ APPROVAL AND SPECS REQ'D
 BY SEC. 2808 FBC 2001.
 7-SPECIFY SAFETY GLASS AS REQUIRED. SEE
 PLANS FOR COMMENTS. SEC. 2405.2 FBC/01
 8-PROVIDE 2 COPIES, SIGNED AND SEALED,
 OF SOIL TEST REPORT. ONLY 1 SUBMITTED.
 9-PROVIDE COMPLETE FLORIDA OR LOCAL
 PRODUCT APPROVAL FOR(NOTE: PROVIDE
 ONLY PRODUCT APPROVAL FOR ITEMS TO BE
 INSTALLED IN THIS PROJECT TO EXPEDITE
 THE REVIEW PROCESS):
 A)SINGLE HUNG WINDOWS. NEED 2 COPIES.
 B)FRENCH DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 **CLARIFY IF USING IMPACT GLAZING.
 **PROVIDE LEGIBLE DRAWINGS.
 C)WINDOW MULLIONS. NEED MATCHING DWGS
 AND CLEARLY INDICATE MULLION SIZE AND
 COMPONENTS TO BE USED.
 D)CLARIFY IF SWINGING DOORS PRODUCT
 APPROVAL SUBMITTED IS FOR ENTRY DOORS.
 IF SO, THEN, CLARIFY WHAT IS THE MEANS
 OF ESCAPE PROVIDED WHEN STORM SHUTTERS
 ARE INSTALLED. SEC. 1005.4.5 FBC 2001.
 **NEED LEGIBLE DRAWINGS.
 E)STORM SHUTTERS: **FLORIDA APPROVAL IS
 PENDING. **CLARIFY INSTALLATION SCHED.
 TO IDENTIFY WHAT'S IMPACT GLAZING OR
 NOT. **CLEARLY IDENTIFY THE MEANS OF
 ESCAPE. **WHICH PRODUCT APPROVAL IS
 GOING TO BE USED. THERE ARE 2.
 **DRAWINGS NEED TO HAVE ENGINEER'S
 ORIGINAL SEAL, SIGNATURE, DATE AS
 REQUIRED BY THE ENGINEER. **WIND LOAD
 SCHEDULE DWG NEEDS TO REVISE THE PEAK
 ROOF HEIGHT. SEE EXTERIOR ELEVATIONS
 FOR CORRECT ONE.
 **CHECK ENGINEERED DRAWINGS FOR LIMITATI
 ONS ON MAXIMUM/MINIMUM PANEL SPAN.
 **NEED LEGIBLE DRAWINGS.
  
 F)CLARIFY WHERE IS THE "IMPACT WALL 3000
 SYSTEM GOING TO BE USED. NEED FLORIDA
 OR LOCAL PRODUCT APPROVAL.
 **IF THIS SYSTEM IS TO BE USED ON FIXED
 WINDOWS AS SHOWN ON PLANS, THEN, NEED
 SEPARATE PRODUCT APPROVAL FOR WINDOWS
 BIGGER THAN THOSE COVER IN THIS REPORT
 G)NEED FLORIDA/LOCAL PRODUCT APPROVAL
 FOR GARAGE DOORS.
 **NEED GARAGE DOORS THAT MEET THE DESIGN
 PRESSURES CALCULATED BY ARCHITECT.
  
 10-SPECIFY ROOF TILE FASTENING. SEE SEC.
 1606.3 FBC 2001 AND SEC. 104.2.1.1
 CITY AMENDMENTS TO FBC 2001.
 11-OWES $613.72 FOR LOW DECLARED VALUE &
 RADON FEES.
 12-SPECIFY HOW IS (3)2X12 AT ENTRY PORCH
 PUT TOGETHER TO FORM BEAM.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 13-SHEET A6.1: A)SPECIFY CONNECTOR FOR
 GIRDER TRUSS. SE PLAN FOR COMMENTS.
 B)PROVIDE COLUMN CAP THAT SUPPORTS TWO
 GIRDER TRUSSES AS SHOWN ON PLAN. SEE
 COMMENTS ON ROOF FRAMING PLAN.
 14-REVISE WINDOW BUCK DETAIL: A) SEE
 SEC. 1707.4.4.2 FBC 2001 FOR PROPER
 BUCK INSTALLATION.
 B)PROVIDE DETAIL THAT CORRECTLY SHOWS
 RELATIONSHIP BETWEEN BUCK AND WALL.
 EG: SEE DOOR DETAIL. DRAWING SHOWS
 BUCK INSTALLED ON A PLAIN WALL WITH
 NO EDGES. SEE COMMENTS ON PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.