| Plan Review Notes For Permit 04010813 |
| Permit Number |
04010813 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-28 00:00:00 | DENIED: | | | 1. ATTIC ACCESS OPENING SHALL BE NO LESS | | | THAN 30" X 22" AS PER 2001 FBC(M) 306.3 | | | | | | 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 - | | | 1. THE SERVICE PANEL OF THE EQUIPMENT IS | | | LOCATED WITHIN 6 FT OF AN ATTIC | | | ACCESS. | | | 2. A DEVICE IS INSTALLED TO ALERT THE | | | OWNER OR SHUT DOWN WHEN THE | | | CONDENSATE DRAIN IS NOT WORKING | | | PROPERLY. | | | 4. A NOTICE IS POSTED ON THE ELECTRIC | | | SERVICE PANEL INDICATING TO THE | | | HOMEOWNER THAT THE AIR HANDLER IS | | | LOCATED IN THE ATTIC. | | | | | | 2. RETURN AIR TO THE MASTER BEDROOM & | | | THE STUDY ARE NOT SIZED PROPERLY. RETURN | | | AIR JUMPERS SHALL BE SIZED 1 1/2 TIMES | | | THE CROSS SECTIONAL AREA (SQ INCHES) OF | | | THE SUPPLY DUCT, PER 2001 FBC(M) 601.4 | | | EXCEPTION #1.THE STUDY REQUIRES A 10" | | | JUMPER INSTEAD OF 8".THE MASTER | | | MASTER BEDROOM IS TO INCLUDE ALL SUPPLY | | | AIR TO THAT AREA THEREFORE THE RETURN | | | JUMPER IS REQUIRED TO BE A MINIMUM OF | | | 15" PER 2001 FBC(M) 601.4 EXCEPTION #1 | | | AND 4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|