2004-01-28 00:00:00DENIED:
 1. ATTIC ACCESS OPENING SHALL BE NO LESS
 THAN 30" X 22" AS PER 2001 FBC(M) 306.3
  
 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 -
 1. THE SERVICE PANEL OF THE EQUIPMENT IS
 LOCATED WITHIN 6 FT OF AN ATTIC
 ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE
 OWNER OR SHUT DOWN WHEN THE
 CONDENSATE DRAIN IS NOT WORKING
 PROPERLY.
 4. A NOTICE IS POSTED ON THE ELECTRIC
 SERVICE PANEL INDICATING TO THE
 HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC.
  
 2. RETURN AIR TO THE MASTER BEDROOM &
 THE STUDY ARE NOT SIZED PROPERLY. RETURN
 AIR JUMPERS SHALL BE SIZED 1 1/2 TIMES
 THE CROSS SECTIONAL AREA (SQ INCHES) OF
 THE SUPPLY DUCT, PER 2001 FBC(M) 601.4
 EXCEPTION #1.THE STUDY REQUIRES A 10"
 JUMPER INSTEAD OF 8".THE MASTER
 MASTER BEDROOM IS TO INCLUDE ALL SUPPLY
 AIR TO THAT AREA THEREFORE THE RETURN
 JUMPER IS REQUIRED TO BE A MINIMUM OF
 15" PER 2001 FBC(M) 601.4 EXCEPTION #1
 AND 4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.