Plan Review Notes
Plan Review Notes For Permit 04010749
Permit Number 04010749
Review Stop P
Sequence Number 8
Notes
Date Text
2004-09-21 00:00:00REVISISON DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 A) SHT P-9 FROM PREVIOUS REVIEW:
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.- MANY LENGTHS ARE NOT
 SHOWN FOR CUT SECTIONS OF PIPES. SEE
 RED LINE MARKS FOR SECTIONS WITH NO
 LENGTHS SHOWN,
 2) SHT P-10 REVISION #4 NOT FOUND.
 PLEASE CLAIRFY. SECTION 104.2.1
 3) SHT P10 NEW EMERGENCY OVERFLOW DRAINS
 SHOWN ON REVISIONS ARE NOT APPROVED.
 ROOF DRAINS L1, L2, L5, L6, & L7 REQUIRE
 50.24 SQ IN, TWO 6" DRAINS PROVIDE 56.54
 SQ IN. BUT FOUR 3" DRAINS ONLY PROVIDE
 28.26 SQ IN. - EMERGENCY OVERFLOW DRAINS
 FOR L3, & L4 REQUIRE 28.26 SQ IN, BUT
 TWO 3" DRAINS ONLY PROVIDE 14.13 SQ IN.
 SECTION 1107
 4) FROM PREVIOUS REVIEW: THE CLEANOUTS
 REQUIRED IN SECTION 708.3.1 ARE NOT TO
 BE DELETED. NO EXCEPTION TO THIS SECTION
 IS NOTED IN THE CODE.
 5) VACUUM RELIEF VALVES REQUIRED BY SEC-
 TION 504.2 ARE NOT SHOWN IN THE PROPER
 LOCATION. THESE VALVES SHALL BE LOCATED
 ON THE SUPPLY SIDE OF THE HEATER AND BE
 ABOVE THE TOP OF THE HEATERS. WATER
 HEATERS ONE AND TWO SHOW THEM INSTALLED
 ON THE HOT WATER SIDE. WATER HEATER
 THREE AND THE STORAGE TANK HAVE NO VAC-
 UUM RELIEF VALVES SHOWN. WILL WATER
 HEATERS ONE AND TWO BE INSTALLED STACKED
 AS SHOWN? WATER HEATERS SHOULD BE INST-
 ALLED SO THAT THEY ARE PIPED IN PARALLEL
 AND THE SUPPLY AND HOT WATER TIE IN THE
 CENTER OF THE HEATERS SO THEY HEAT AND
 ARE USED SIMULTAINIOUSLY. SECTION 104.2.
 1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]