| Plan Review Notes For Permit 04010749 |
| Permit Number |
04010749 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-03-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT P-16 LOWER ROOF ON N-WEST SIDE | | | SHOWS 6" STORM DRAIN, THEN AFTER SECOND | | | ROOF DRAIN SHOWS 4" STORM DRAIN. MINIMUM | | | 8" STORM DRAIN REQUIRED AFTER SECOND | | | ROOF DRAIN. | | | 2) SHT P-9 STORM DRAIN LINE FROM (L5) | | | ADDS (L8) OUTSIDE BLDG. THIS DRAIN WAS | | | NOT FOUND. PLEASE CLAIRFY AND INDICATE | | | WHERE L8 CAN BE LOCATED. | | | 3) MEASUREMENTS STILL MISSING FOR SOME | | | ACCESSIBLE FIXTURES. NOT HEIGHT SHOWN | | | FOR URINAL 11-4.18.2, HEIGHT & CLEARANC- | | | ES FOR LAVS 11-4.19.2, EXPOSED PIPES AND | | | SURFACES 11-4.19.4, SPOUT HEIGHT FOR THE | | | DRINKING FOUNTAIN 11-4.15.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|