Plan Review Notes
Plan Review Notes For Permit 04010749
Permit Number 04010749
Review Stop P
Sequence Number 3
Notes
Date Text
2004-03-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT P-16 LOWER ROOF ON N-WEST SIDE
 SHOWS 6" STORM DRAIN, THEN AFTER SECOND
 ROOF DRAIN SHOWS 4" STORM DRAIN. MINIMUM
 8" STORM DRAIN REQUIRED AFTER SECOND
 ROOF DRAIN.
 2) SHT P-9 STORM DRAIN LINE FROM (L5)
 ADDS (L8) OUTSIDE BLDG. THIS DRAIN WAS
 NOT FOUND. PLEASE CLAIRFY AND INDICATE
 WHERE L8 CAN BE LOCATED.
 3) MEASUREMENTS STILL MISSING FOR SOME
 ACCESSIBLE FIXTURES. NOT HEIGHT SHOWN
 FOR URINAL 11-4.18.2, HEIGHT & CLEARANC-
 ES FOR LAVS 11-4.19.2, EXPOSED PIPES AND
 SURFACES 11-4.19.4, SPOUT HEIGHT FOR THE
 DRINKING FOUNTAIN 11-4.15.2
  