Plan Review Notes
Plan Review Notes For Permit 04010749
Permit Number 04010749
Review Stop E
Sequence Number 3
Notes
Date Text
2004-08-13 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE THERE ARE SOME SHEETS
 WHERE A REVISION IS NOTED ON TITLE
 BLOCK, BUT WAS NOT ABLE TO LOCATE A
 REV#/CLOUD/TRIANGLE ON PLAN.
 SHEETS: E-3,E-4,E-11
  
 2)NOTE: PLEASE SEE NEW PANELS NOW WHICH
 HAVE BEEN ADDED TO RISER. 2R2,3R3,4R4,
 THESE PANELS WERE ADDED ON PREVIOUS
 REVISED PLANS HOWEVER THERE IS NO
 INDICATION ON PANELS 2R2,3R2,4R2 IF THEY
 ALSO CONATIN FEED-THRU LUGS OR IF THESE
 PANELS CONTAIN OCP FOR SUB-FEEDS?
 **PLEASE ALSO SEE THESEPANELS ARE NOT
 INCLUDED ON FLR PLANS FOR ELECTRICAL
 ROOMS.
  
 3)NOTE: PLEASE SEE NOTE # 7 FROM FIRST
 REVIEW. PANEL LR IS STILL BEING SHOWN
 AS BEING A 100A RATED PANEL WITH A 125A
 FEED FROM MDP. PLEASE SEE MDP SCHEDULE
 WHICH INDICATES 125A BRKR.
 THIS WAS NOT CORRECTED FROM FIRST REVIEW
 408.13
  
 4)NOTE:PLEASE ADD NOTE WIND LOADS TO
 MEET 140MPH ON SITE PLAN ELECTRICAL
 LT POLES.
  
 **POOL UNDER SEPARATE PERMIT, INCLUDING
 ELECTRICAL.
 AN ELECTRICAL WILL BE REQUIRED AT THAT
 TIME WITH A SEPARATE POOL EQUIPMENT
 WIRING DIAGRAM.
 **THIS IS ONLY A NOTE***
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AN
 ONLY INSERT NEW REVISED SHEEST INTO
 COMPLETED SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]