| 2004-08-13 00:00:00 | ************ UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE THERE ARE SOME SHEETS |
| | WHERE A REVISION IS NOTED ON TITLE |
| | BLOCK, BUT WAS NOT ABLE TO LOCATE A |
| | REV#/CLOUD/TRIANGLE ON PLAN. |
| | SHEETS: E-3,E-4,E-11 |
| | |
| | 2)NOTE: PLEASE SEE NEW PANELS NOW WHICH |
| | HAVE BEEN ADDED TO RISER. 2R2,3R3,4R4, |
| | THESE PANELS WERE ADDED ON PREVIOUS |
| | REVISED PLANS HOWEVER THERE IS NO |
| | INDICATION ON PANELS 2R2,3R2,4R2 IF THEY |
| | ALSO CONATIN FEED-THRU LUGS OR IF THESE |
| | PANELS CONTAIN OCP FOR SUB-FEEDS? |
| | **PLEASE ALSO SEE THESEPANELS ARE NOT |
| | INCLUDED ON FLR PLANS FOR ELECTRICAL |
| | ROOMS. |
| | |
| | 3)NOTE: PLEASE SEE NOTE # 7 FROM FIRST |
| | REVIEW. PANEL LR IS STILL BEING SHOWN |
| | AS BEING A 100A RATED PANEL WITH A 125A |
| | FEED FROM MDP. PLEASE SEE MDP SCHEDULE |
| | WHICH INDICATES 125A BRKR. |
| | THIS WAS NOT CORRECTED FROM FIRST REVIEW |
| | 408.13 |
| | |
| | 4)NOTE:PLEASE ADD NOTE WIND LOADS TO |
| | MEET 140MPH ON SITE PLAN ELECTRICAL |
| | LT POLES. |
| | |
| | **POOL UNDER SEPARATE PERMIT, INCLUDING |
| | ELECTRICAL. |
| | AN ELECTRICAL WILL BE REQUIRED AT THAT |
| | TIME WITH A SEPARATE POOL EQUIPMENT |
| | WIRING DIAGRAM. |
| | **THIS IS ONLY A NOTE*** |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AN |
| | ONLY INSERT NEW REVISED SHEEST INTO |
| | COMPLETED SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |