| Date |
Text |
| 2004-03-15 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | A) FOLLOWING COMMENTS WERE NOT ADDRESSED |
| | OR COMMENT RESPONSE WAS NOT FOUND OR NOT |
| | ADDRESSED PROPERLY. THE COMMENT NUMBER |
| | FROM FIRST REVIEW WILL BE SHOWN TO AVOID |
| | CONFUSION. |
| | 2) SHOW COMPLIANCE WITH SECTION 11-9.1.3 |
| | ACCOMMODATIONS FOR PERSONS WITH HEARING |
| | IMPAIRMENT. - RESPONSE NOTED - FOUND 4 |
| | UNITS PLUS ONE ACCESSIBLE UNIT WITH THIS |
| | ACCOMODATION. ONE ADDITIONAL UNIT WILL |
| | BE REQUIRED SEPARATE FROM ACCESSIBLE |
| | UNITS PER SECTION11-9.1.3 |
| | 4) SHT A-5 SUBMIT CALCULATIONS FOR LOWER |
| | ROOFS PER SECTION 1106 AND ALL SUBSECT- |
| | IONS. SHOW 1/2 AREA OF VERTICAL WALL |
| | ADDED TO SQUARE FOOTAGE OF ROOF IN CAL- |
| | CULATIONS. - NO CALCULATIONS WERE FOUND |
| | IN MECHANICAL PLANS. INDICATE SPECIFIC |
| | SHEET RESPONSE IS LOCATED. - PER CONVER- |
| | SATION WITH STEVE SHEET P-16 WILL BE |
| | SUBMITTED WITH THIS INFO. |
| | 5) SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 |
| | AND 1107 AND ALL SUBSECTIONS. - RESPONSE |
| | TO SCUPPER COMMENT SEEN - BLDG OFFICIAL |
| | THINKS THAT IT WILL BE A LEAK PROBLEM. |
| | HE SAYS THAT A TROUGH MAY BE A BETTER |
| | SOLUTION. SUBMIT A DETAIL WITH MEASURE- |
| | MENTS SHOWING COVERAGE OF 6" PIPE ECT IF |
| | THIS IS THE SECONDARY DRAIN STILL WANTED |
| | 6) SHTS A-27 & A-28 SHOW MEASUREMENTS |
| | FOR FIXTURES PER SEC'S 11-4.15, 11-4.16, |
| | 11-4.18, 11-4.19, & 11-4.23 AND ALL SUB- |
| | SECTIONS. SHOW CLEAR FLOOR SPACE FOR ALL |
| | ACCESSIBLLE FIXTURES INCLUDING DRINKING |
| | FOUNTAINS, URNALS ECT. - RESPONSE NOTED |
| | SOME CLEAR FLOOR SPACES NOT SHOWN. ROOM |
| | 117 EMPLOYEE LOUNGE SHOW CLEAR FLOOR |
| | FOR SINK. SHT A-12 KING DELUX ACCESSIBLE |
| | SHOW 5' TURNING AREA. SHT A-11 SHOW |
| | CLEAR FLOOR SPACE AT DRINKING FOUNTAINS. |
| | SHT A-15 SHOW CLEAR FLOOR SPACE FOR THE |
| | URINAL ROOM 114. |
| | 10) SHT P-9 SEPARATE GAS PERMIT REQUIRED |
| | FOLLOWING INFORMATION REQUIRED FOR THE |
| | GAS PERMIT. |
| | B) SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED.- NO MATERIAL FOR PIPE LOCATED |
| | C) SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR PER FBC-2001 FUEL GAS CODE SECTION |
| | 304. - RESPONSE NOTED. SHT M-1 CALCULAT- |
| | IONS INDICATE 2 DRYERS, BUT SHT P-9 GAS |
| | RISER SHOWS 3 DRYERS @ 165K BTU'S EACH |
| | PLEASE CLAIRFY. - ALSO 124 SQUARE INCHES |
| | IS REQUIRED AT DRYER IF VERTICAL DUCT |
| | BUT IF HORIZONTAL DUCT 247.5 SQ IN REQD. |
| | 10" DUCT VERT WILL SUPPLY 78.5 SQ. IN. |
| | PLEASE SUBMIT DETAIL FOR DUCT. INDICATE |
| | IF VERTICAL OR HORIZONTAL, AND IF AIR |
| | IS OUTSIDE OR INSIDE AIR SUPPLYING THE |
| | COMBUSTION AIR. - SHOW COMBUSTION AIR |
| | CALCULATIONS FOR THE 80K BTU'S IN THE |
| | GUEST LAUNDRY ROOM. |
| | E) SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2- RE- |
| | SPONSE NOTED, BUT NO MANUF. SHEETS WERE |
| | FOUND IN MECH. SHEETS. |
| | 12) SHT P-10 ROOF DRAIN AND SQUARE FOOT- |
| | AGE NOT SHOWN FOR ROOF BELOW AT ENTRANCE |
| | 16) LOCATION OF WATER HAMMER ARRESTORS |
| | SHALL BE NEAR THE FIXTURES IN AN |
| | "EFFECTIVE RANGE" NOT IN CEILING AS |
| | SHOWN. PDI-WH 201 AND MANUF. INSTALL. |
| | INSTRUCTIONS. |
| | 17) SHT P-14 VACUUM RELIEF VALVES REQUI- |
| | RED FOR BOTTOM FED WATER HEATERS. SEC |
| | 504.2 - RESPONSE NOTED, BUT THIS HAS NOT |
| | BEEN ADDRESSED. |
| | 18) WATER HAMMER ARRESTORS SHALL BE |
| | LOCATED NEAR FIXTURE NOT IN CEILING. |
| | PDI-WH 201 AND MANUF. INSTALL. INSTRUCT. |
| | 19) SEE COMMENTS 16 & 18. |
| | |