| Plan Review Notes For Permit 04010749 |
| Permit Number |
04010749 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-03-12 00:00:00 | 1) THE FP-1 PAGE DOES NOT CORRESPOND | | | WITH C-2. | | | | | | 2) IS THE FIRE STANDPIPE/ SPRINKLER | | | ISOMETRIC DRAWING CORRECT. | | | | | | 3) STORAGE ROOM AND SUNDRIES STORAGE | | | NOT PROTECTED BY FIRE SPRINKLERS. | | | | | | 4) MEN'S AND WOMEN'S RESTROOM 163 | | | AND 164 NOT SPRINKLER PROTECTED. | | | | | | 5) ALL SMOKE DETECTORS SHALL BE | | | INSTALLED A MINIMUM OF THREE FEET | | | FROM AC DIFFUSERS. | | | | | | 6) PLEASE VERIFY TYPICAL ELECTRICAL | | | DRAWINGS ON PAGE E-7 AND VERIFY | | | THAT ENOUGH SMOKE DETECTORS ARE | | | PRESENT. | | | | | | 7) SOME EXIT SIGNS APPEAR TO BE | | | MISSING FROM THE FIRST FLOOR. | | | | | | 8) SMOKE DETECTOR MISSING FROM STORAGE | | | ROOM 113. | | | | | | 9) BUILDING ADDRESS REQUIRED. A MINIMUM | | | OF 6" NUMBERS REQUIRED. | | | | | | 10) LOCKING DEVICES ON EXIT DOORS TO | | | COMPLY WITH THE LIFE SAFETY CODE. | | | | | | 11) PLEASE DISPLAY ALL AVAILABLE | | | FIRE HYDRANTS LOCATED NEAR THE SITE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|