2004-03-12 00:00:001) THE FP-1 PAGE DOES NOT CORRESPOND
 WITH C-2.
  
 2) IS THE FIRE STANDPIPE/ SPRINKLER
 ISOMETRIC DRAWING CORRECT.
  
 3) STORAGE ROOM AND SUNDRIES STORAGE
 NOT PROTECTED BY FIRE SPRINKLERS.
  
 4) MEN'S AND WOMEN'S RESTROOM 163
 AND 164 NOT SPRINKLER PROTECTED.
  
 5) ALL SMOKE DETECTORS SHALL BE
 INSTALLED A MINIMUM OF THREE FEET
 FROM AC DIFFUSERS.
  
 6) PLEASE VERIFY TYPICAL ELECTRICAL
 DRAWINGS ON PAGE E-7 AND VERIFY
 THAT ENOUGH SMOKE DETECTORS ARE
 PRESENT.
  
 7) SOME EXIT SIGNS APPEAR TO BE
 MISSING FROM THE FIRST FLOOR.
  
 8) SMOKE DETECTOR MISSING FROM STORAGE
 ROOM 113.
  
 9) BUILDING ADDRESS REQUIRED. A MINIMUM
 OF 6" NUMBERS REQUIRED.
  
 10) LOCKING DEVICES ON EXIT DOORS TO
 COMPLY WITH THE LIFE SAFETY CODE.
  
 11) PLEASE DISPLAY ALL AVAILABLE
 FIRE HYDRANTS LOCATED NEAR THE SITE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910