| Notes |
| Date |
Text |
| 2004-10-15 00:00:00 | REVISIONS OK FOR SHEETS P-10, P-12, P-14 | | | & P-16 - DENIED P-9 | | | | | | REVISION DENIED | | | | | | SHT P-9 GAS RISER DIAGRAM DENIED. 2" RE- | | | QUIRED UP TO FIRST DRYER AND 1-1/2" RE- | | | QUIRED UP TO SECOND DRYER. - NFPA NOT | | | ADOPTED FOR GAS SIZING, AND PIPING SHALL | | | BE SIZED BY FBC-2001 FUEL GAS CODE TABLE | | | 402(2). - RESIZE PIPING PER APPROVED | | | CODE TABLE AND RESUBMIT GAS RISER REVIS- | | | ION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|