| 2004-01-30 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHOW COMPLIANCE WITH SECTION 11-9.1.4 |
| | CLASSES OF SLEEPING ACCOMMODATION. THE |
| | "KING SUITE DELUXE UNITS" HAVE NOT BEEN |
| | SHOWN TO HAVE ANY ACCESSIBLE UNITS. |
| | 2) SHOW COMPLIANCE WITH SECTION 11-9.1.3 |
| | ACCOMMODATIONS FOR PERSONS WITH HEARING |
| | IMPAIRMENT. |
| | 3) SHOW COMPLIANCE WITH SECTION 11-9.2.3 |
| | ONE UNIT REQUIRED UNDER THIS SECTION. |
| | 4) SHT A-5 SUBMIT CALCULATIONS FOR LOWER |
| | ROOF PER SEC 1106 AND ALL SUBSECTIONS. |
| | SHOW 1/2 AREA OF VERTICAL WALL ADDED TO |
| | SQUARE FOOTAGE OF ROOF IN CALCULATIONS. |
| | 5) SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 |
| | AND 1107 AND ALL SUBSECTIONS. - SCUPPERS |
| | ARE 36 FEET OR MORE FROM SOME OF THE |
| | ROOF DRAINS. AT 1/4" PER FOOT SLOPE AND |
| | THE SCUPPERS 2" TO 4" TO FLOW LINE, THE |
| | PONDING WILL BE APPROXIMATELY 13" DEEP |
| | NEAR THE DRAIN. THIS WILL PLACE WEIGHT |
| | OF 4.5 TO 6 INCHES OF WATER ON ROOF BE- |
| | FOR THE RAIN WATER WILL START TO DRAIN |
| | THRU THE SCUPPERS. SUBMIT CALCULATIONS |
| | FOR ROOF TO SHOW IT WILL SUPPORT THIS |
| | WEIGHT. |
| | 6) SHTS A-27 & A-28 SHOW MEASUREMENTS |
| | FOR FIXTURES PER SEC'S 11-4.15, 11-4.16, |
| | 11-4.18, 11-4.19, AND 11-4.23 AND ALL |
| | SUBSECTIONS. SHOW CLEAR FLOOR SPACE FOR |
| | ALL ACCESSIBLE FIXTURES INCLUDING DRINK- |
| | ING FOUNTAINS, URNALS ECT. |
| | 7) SHTS A-15.1 & A-28 PRIVATE BATHROOM |
| | SHALL BE ADAPTABLE. SHOW DETAIL FOR |
| | SHOWER BACKING, CURB, VALVE HEIGHT, AND |
| | OPENING FOR WATER CLOSET AND CLEAR FLOOR |
| | SPACE AND TURNING AREA ECT. |
| | 8) SHT A-34 SEPARATE PLANS & PERMIT REQ- |
| | UIRED FOR POOL. PLANS TO BE SUBMITTED TO |
| | PALM BEACH COUNTY HEALTH DEPT. FOR APP- |
| | ROVAL PRIOR TO SUBMITTING TO CITY WPB |
| | FOR REVIEW. |
| | 9) SHT P-1 PLUMBING NOTES #13, AIR |
| | CHAMBERS ARE NOT APPROVED. DELETE FROM |
| | NOTES. SECTION 604.9 |
| | 10) SHT P-9 SEPARATE GAS PERMIT REQUIRED |
| | FOLLOWING INFORMATION REQUIRED FOR THE |
| | PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED AND ALL PIPE SIZES. (RECOMMEND |
| | THAT A 2 POUND SYSTEM BE USED AS THIS |
| | WILL REDUCE THE PIPE SIZE) |
| | C. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | D. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | 11) SEPARATE IRRIGATION PLANS AND PERMIT |
| | ARE REQUIRED. |
| | 12) SHT P-10 ROOF DRAIN AND SQUARE FOOT- |
| | AGE NOT SHOWN FOR ROOF BELOW AT ENTRANCE |
| | 13) SHT P-11 IDENTIFY FIXTURES ON SANT. |
| | RISER S/15. |
| | 14) SHT P-11 FLOOR DRAINS NOT APPROVED |
| | FOR INDIRECT WASTE. SECTIONS 802.3 AND |
| | 802.3.2 |
| | 15) SHT P-11 FIXTURE UNITS ARE NOT CORR- |
| | ECT FOR SANT. RISERS S/5 THRU S-14. THE |
| | WATER CLOSETS ARE 4DFU NOT 3DFU. ADJUST |
| | FIXTURE UNITS ON RISERS, AND FIXTURE |
| | UNITS ACCUMULATED IN BLDG DRAIN ON SHT |
| | P-12. 6" PIPE REQUIRED @ 186 FU WHERE IT |
| | SHOWS 4" @ 159 FU. |
| | 16) SHT P-13 DOMESTIC WATER RISER, AIR |
| | CHAMBERS ARE NOT APPROVED. DELETE FROM |
| | RISER DIAGRAM. SECTION 604.9 - WATER |
| | HAMMER ARRESTORS ARE REQUIRED AT ALL |
| | QUICK CLOSING VALVES, (WASH MACHINES, |
| | ICE MAKERS, AND DISH WASHERS), & LOCATED |
| | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" |
| | NOT IN THE CEILING. PDI-WH 201 AND MANUF |
| | INSTALLATION INSTRUCTIONS. |
| | 17) SHT P-14 VACUUM RELIEF VALVES REQUI- |
| | RED FOR BOTTOM FED WATER HEATERS. SECT- |
| | ION 504.2 |
| | 18) SHT P-14 ISOMETRIC WATER DIAGRAM, |
| | AIR CHAMBERS AT POOL SHOWER NOT APPROVED |
| | DELETE. 604.9 |
| | 19) SHT P-15 DOMESTIC WATER ISOMETRIC |
| | DIAGRAMS, AIR CHAMBERS ARE NOT APPROVED. |
| | DELETE FROM RISERS. |
| | |
| | REVIEW BY KEN STEVENS |