| Plan Review Notes For Permit 04010749 |
| Permit Number |
04010749 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-21 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | LETTER FROM ANDREW J. YOUNGROSS P.E. | | | DATED DECEMBER 16, 2004 CHANGING THE | | | MAIN 3" SHUT OFF VALVE FOR THE GAS | | | SYSTEM IS NOT ACCEPTABLE. PER TABLE | | | 402(2) THE MAXIMUM BTU'S ALLOWED FOR 2" | | | PIPE AND VALVE IS 1,020,000 BTU'S AND | | | THE TOTAL BTU LOAD ON THE SYSTEM IS | | | 2,195,000 BTU'S. A 3" SOV IS REQUIRED. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|