Plan Review Notes
Plan Review Notes For Permit 04010749
Permit Number 04010749
Review Stop G
Sequence Number 1
Notes
Date Text
2004-12-21 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 LETTER FROM ANDREW J. YOUNGROSS P.E.
 DATED DECEMBER 16, 2004 CHANGING THE
 MAIN 3" SHUT OFF VALVE FOR THE GAS
 SYSTEM IS NOT ACCEPTABLE. PER TABLE
 402(2) THE MAXIMUM BTU'S ALLOWED FOR 2"
 PIPE AND VALVE IS 1,020,000 BTU'S AND
 THE TOTAL BTU LOAD ON THE SYSTEM IS
 2,195,000 BTU'S. A 3" SOV IS REQUIRED.
  
  
 REVIEW BY KEN STEVENS