| 2004-01-16 00:00:00 | 1) TEMPORARY STANDPIPE SYSTEM IS |
| | REQUIRED WHEN THE BUILDING REACHES |
| | THREE FLOORS OR 30 FEET IN HEIGHT |
| | WHILE THE BUILDING IS UNDER |
| | CONSTRUCTION. |
| | |
| | 2) CONSTRUCTION, DEMOLITION, AND |
| | RENOVATION TO COMPLY WITH NFPA 241. |
| | |
| | 3) BUILDING ADDRESS REQUIRED. |
| | |
| | 4) A KNOX-BOX WILL BE REQUIRED. |
| | |
| | 5) TACTILE SIGNAGE REQUIRED AT ALL |
| | STAIRWELLS. |
| | |
| | 6) EMERGENCY INSTRUCTIONS FOR GUESTS |
| | SHALL BE POSTED. |
| | |
| | 7) ALL GUEST LAUNDRIES GREATER THAN |
| | 100 SQUARE FEET SHALL BE PROTECTED |
| | WITH ONE HOUR CONSTRUCTION AND |
| | FIRE SPRINKLERS. MAINTENANCE SHOPS |
| | AND TRASH COLLECTION ROOMS SHALL HAVE |
| | ONE HOUR CONSTRUCTION AND SPRINKLERS. |
| | |
| | 8) STANDPIPE SYSTEM HOSE VALVES SHALL |
| | BE PLACED WITHIN STAIRWELLS ON |
| | EVERY FLOOR. |
| | |
| | 9) THE COVERED OVERHANG SHALL BE AT |
| | LEAST 13'- 6" SO FIRE AND PARAMEDICAL |
| | CAN PASS UNDERNEATH IT. |
| | |
| | 10) PLEASE INDICATE INTERIOR FINISH |
| | FOR WALLS AND CEILINGS. |
| | |
| | 11) ANY AREAS OF REFUGE SHALL MEET |
| | ALL OF THE REQUIREMENTS OF THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | |
| | 12) ALL GUESTROOMS FOR HEARING |
| | IMPAIRED SHALL BE PROVIDED WITH |
| | FIRE ALARM VISUAL APPLIANCES. |
| | |
| | 13) PLEASE PROVIDE PRESCRIPTIVE |
| | DETAILS FOR ALL HANDRAILS AND |
| | GUARDRAILS. |
| | |
| | 14) SOME BATHROOMS ARE SPRINKLER |
| | PROTECTED IN GUESTROOMS AND SOME ARE |
| | NOT. PLEASE EXPLAIN RATIONALE. |
| | |
| | 15) BATHROOMS 163 AND 164 ARE NOT |
| | FIRE SPRINKLER PROTECTED. WHY? |
| | |
| | 16) THE FDC IS NOT SHOWN ON FIRST |
| | FLOOR FIRE SPRINKLER PLAN. WHY? |
| | |
| | 17) NOTE # 11 ON PAGE FA-4 IS NOT |
| | CORRECT. DUCT DETECTORS WHEN ACTIVATED |
| | SHALL CAUSE A GENERAL ALARM. |
| | |
| | 18) FIRE ALARM CIRCUITS SHALL BE |
| | CLASS A OR FULLY ADDRESSABLE. NOTE |
| | # 8 ON PAGE FA-4 INDICATES CIRCUITS |
| | WILL BE CLASS B. |
| | |
| | 19) THE FIRE ALARM SYSTEM SHALL BE |
| | UL LISTED FOR CENTRAL STATION SERVICE. |
| | |
| | 20) ELEVATOR WARNING SIGNS REQUIRED |
| | AT ELEVATORS. |
| | |
| | 21) SINGLE STATION SMOKE DETECTORS |
| | ARE REQUIRED IN EVERY LIVING AREA |
| | AND SLEEPING ROOM WITHIN GUEST SUITE. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |