| 2004-01-29 00:00:00 | ************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE FIRE REVIEW NOTESAND |
| | NOTES FROM OTHER REVIEWERS THAT MAY HAVE |
| | AN AFFECT ON ELECTRICAL PLANS. |
| | |
| | 2)NOTE: PLEASE SEE PANEL EQA IS SHOWN |
| | ON RISER BUT COULD NOT BE LOCATED ON |
| | PLANS. |
| | |
| | 3)NOTE: PLEASE ALSO SEE PANELS SHOWN |
| | ON RISER FOR 2ND, 3RD, AND 4TH FLR |
| | COULD NOT BE LOCATED ON PLANS. |
| | |
| | 4)NOTE: PLEASE CLARIFY LOCATION FOR |
| | A/C EQUIPMENT. 210.63 |
| | |
| | 5)NOTE: PLEASE SEE RISER SHOWS TWO |
| | "MAINS 1 OF 2". (MISPRINT) |
| | |
| | 6)NOTE: PLEASE SEE PANEL 1R1. RISER |
| | APPEARS TO SHOW THIS FEEDING1R2 BUT |
| | PANEL DOES NOT INDICATE BEING "FEED THRU |
| | LUGS". PLEASE CLARIFY. |
| | |
| | 7)NOTE: PLEASE CORRELATE ALL PANELS ON |
| | RISER DIAGRAM WITH INFORMATION GIVEN |
| | ON PANEL SCHEDULES. MANY PANELS ON |
| | RISER ARE SHOWN W/ DIFFERENT AMPERAGE |
| | RATINGS,THAN WHAT IS SHOWN ON PANELS. |
| | EQA,EQ,LDY,L,LR,4AC2,3AC2,2AC2 . |
| | PLEASE SEE LR SHOWN AS 100 WITH 125A |
| | FEED. |
| | |
| | 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | AIC RATING IS SHOWN FOR MAIN, HOWEVER NO |
| | INFORMATION FOR PANEL AND BRANCH BRKRS |
| | ARE SHOWN. THYE ARE BLANK. |
| | |
| | 9)NOTE: PLEASE PROVIDE INFORMATION ON |
| | ENCLOUSURE/GUTTER FOR WHAT APPEARS TO |
| | BE TAPS TO ELEVATOR MOTORS. PLEASE ALSO |
| | PROVIDE AIC RATING AND MORE INFORMATION |
| | FOR MAIN 1 OF 2 FOR ELEVATORS. |
| | 110.9 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |