Plan Review Notes
Plan Review Notes For Permit 04010749
Permit Number 04010749
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-29 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE SEE FIRE REVIEW NOTESAND
 NOTES FROM OTHER REVIEWERS THAT MAY HAVE
 AN AFFECT ON ELECTRICAL PLANS.
  
 2)NOTE: PLEASE SEE PANEL EQA IS SHOWN
 ON RISER BUT COULD NOT BE LOCATED ON
 PLANS.
  
 3)NOTE: PLEASE ALSO SEE PANELS SHOWN
 ON RISER FOR 2ND, 3RD, AND 4TH FLR
 COULD NOT BE LOCATED ON PLANS.
  
 4)NOTE: PLEASE CLARIFY LOCATION FOR
 A/C EQUIPMENT. 210.63
  
 5)NOTE: PLEASE SEE RISER SHOWS TWO
 "MAINS 1 OF 2". (MISPRINT)
  
 6)NOTE: PLEASE SEE PANEL 1R1. RISER
 APPEARS TO SHOW THIS FEEDING1R2 BUT
 PANEL DOES NOT INDICATE BEING "FEED THRU
 LUGS". PLEASE CLARIFY.
  
 7)NOTE: PLEASE CORRELATE ALL PANELS ON
 RISER DIAGRAM WITH INFORMATION GIVEN
 ON PANEL SCHEDULES. MANY PANELS ON
 RISER ARE SHOWN W/ DIFFERENT AMPERAGE
 RATINGS,THAN WHAT IS SHOWN ON PANELS.
 EQA,EQ,LDY,L,LR,4AC2,3AC2,2AC2 .
 PLEASE SEE LR SHOWN AS 100 WITH 125A
 FEED.
  
 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATING IS SHOWN FOR MAIN, HOWEVER NO
 INFORMATION FOR PANEL AND BRANCH BRKRS
 ARE SHOWN. THYE ARE BLANK.
  
 9)NOTE: PLEASE PROVIDE INFORMATION ON
 ENCLOUSURE/GUTTER FOR WHAT APPEARS TO
 BE TAPS TO ELEVATOR MOTORS. PLEASE ALSO
 PROVIDE AIC RATING AND MORE INFORMATION
 FOR MAIN 1 OF 2 FOR ELEVATORS.
 110.9
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW