2005-03-16 00:00:00****CORRECTIONS****
 TRUSS SUBMITTAL DATED 3/11/05 SIGNED BY
 ALI YEMENICILER, PE
  
 1.)SEE PREVIOUS LIST.THE PLATES
 INCREASE USING THE FBC2001/ANSI95 CODE
 USES THE STRESS INCREASE FOR STEEL WHICH
 IS NOT ALLOWED.IF YOU HAVE QUESTIONS,
 PLEASE CALL GABY, CHIEF ENGINEER FOR
 MITEK, 314-851-7493.
  
 2.)SEE PREVIOUS LIST.AN ORIGINAL
 SIGNATURE AND TITLE BLOCK ARE REQUIRED
 FOR THE ENGINEER, FAC61G15-23.002.
  
 3.)IT IS UNCLEAR AS TO WHY I HAVE HAD
 DISCUSSIONS WITH HASAN (WHO REPRESENTED
 HIMSELF AS THE OWNER OF QUALITY TRUSS)
 AND THE PREVIOUS ENGINEER (YEKTA
 KAVASOGLU, PE) REGARDING THE STRESS
 INCREASE ISSUE, YET CALCULATIONS
 CONTINUE TO BE SUBMITTED NONCOMPLIANT.
 IF MY UNDERSTANDING OF THIS ISSUE IS
 INCORRECT, PLEASE ADVISE.
  
  
  