2005-03-03 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
  
 1.)THE TRUSS PACKAGE SUBMITTED DOES
 NOT APPEAR TO BE CODE COMPLIANT.BCLL
 OF 10 IS REQUIRED, FBC TABLE 1604.1.
 THIS CANNOT BE A NONCONCURRENT LOAD AS
 INDICATED IN NOTE 4.ALSO NOTE 4 REFERS
 TO UBC94; THIS CODE IS NOT USED IN
 FLORIDA.GOVERNING CODE IS FBC2001.
  
 2.)THE CODE USED FOR THE ENGINEERING
 WAS FBC2001/ANSI95.YOU CANNOT USE
 ANSI95 AS THIS TAKES THE STRESS INCREASE
 FOR STEEL, 33%.AS PER MY CONVERSATION
 WITH MITEK, THE CORRECT STANDARD IS
 TPI2002.
  
 3.)THE SIGNATURE IS A PHOTOCOPY, NOT
 ALLOWED AS PER FAC61G15-23.002L.A
 TITLE BLOCK IS REQUIRED FOR EACH SHEET.
 REVISE THE TRUSS ENGINEERING AND SUBMIT
 FOR REVIEW.
  
 4.)THE TRUSS DRAWINGS ARE TO BE
 REVIEWED BY ENGINEER OF RECORD,
 FAC61G15-31.002(2).
  
 5.)REGARDING THE APPLICATION FOR LOCAL
 PRODUCT APPROVAL, I WAS UNABLE TO FIND
 STEPHEN D. FISHER, PE/MARVIN LUMBER AND
 CEDAR ON THE WEBSITE AS AN APPROVED
 THIRD PARTY QUALITY ASSURANCE ENTITY,
 FAC9B72.
  
 6.)THE APPLICATION FOR LOCAL PRODUCT
 APPROVAL STATES THAT IT IS FOR THE
 DOUBLE HUNG WINDOWS BUT THE DOCUMENTS
 SUBMITTED ARE FOR MULLIONS ONLY, SEE THE
 EVALUATION REPORT, LIMITATIONS AND
 CONDITIONS OF USE, ITEM 1.TEST REPORTS
 AND SEPARATE APPLICATION REQUIRED FOR
 THE WINDOWS, FBC1704.2.1.
  
 7.)ALL DOCUMENTS PREPARED BY AN
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD
 ARE TO BE ORIGINAL, SIGNED AND SEALED,
 FAC61G15-23.002.
  
 8.)9B-72 DEFINITIONS, TEST REPORT IS
 TO BE BY AN APPROVED TESTING LABORATORY,
 9B72.010(31).THE EVALUATION REPORT
 REFERS TO AN INHOUSE TEST REPORT AND AN
 ANALYSIS AND EXCEL FILE.PROVIDE
 DOCUMENTATION USED FOR THE EVALUATION AS
 PER FAC9B72(5)(D).