2004-02-02 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SEE ALL LOADS ON PANEL
 SCHEDULE INDICATE 120V LOADS WERE FIGUR-
 -ED AT 230V.
 PLEASE ALSO SEE PANEL IS SHOWN @ 120/240
 VTS AND LOAD CALCS FIGS SHOW 230V
 AMPERAGES FOR ALL 120V SHOULD REFLECT
 120V AMPERAGE.
  
 2)NOTE: PLEASE LIST THE REQ'D ARC FAULT
 PROTECTED CIRCUIT(S) PER 210.12
  
 3)NOTE: PLEASE CORRELATE KW RATINGS
 FOR NEW AHU. SHOWS 10KW ON A/C PLANS AND
 FIGURES TO BE 7.5 KW ON ELECTRICAL LOAD
 CALCULATIONS.
  
 4)NOTE: PLEASE SEE WATER HEATER, SHOWS
 5KW , W/ 2P 45A BRKR AND #6 AWG.
 PLEASE SEE THAT MAX OCP FOR WATER HEATER
 IS 150%.MIN 125% 422.13, MAX 150% 422.
 11
  
 5)NOTE: RISER DIAGRAM INDICATES NEW MAIN
 YET PLANS ONLY INDICATE A METER SHOWN
 ON SIDE OF DWELLING. PLEASE SHOW LOCAT-
 -ION OF MAIN.
  
 6)NOTE: PLEASE NOTE: THIS IS A NOTE AND
 NOT FOR ELECTRICAL PLANS. IF PLANS ARE
 SIGNED, DATED AND SEALED BY ARCH, THEN
 THOSE PLANS (MECH) MUST CONTAIN SAME
 TITLE BLOCK AS SET FORTH ON OTHER SHEETS
 AS PER FAC 61G1-16.004. THIS IS ONLY
 A NOTE: NOT FOR ELECTRICAL. TITLE BLOCK
 IS SHOWN ON ELECTRICAL PLANS CORRECTLY.
  
 7)NOTE: PLEASE CLARIFY NEW J-BOX SHOWN
 ON RISER, WHAT DOES THIS DO?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  