| 2004-02-02 00:00:00 | *************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SEE ALL LOADS ON PANEL |
| | SCHEDULE INDICATE 120V LOADS WERE FIGUR- |
| | -ED AT 230V. |
| | PLEASE ALSO SEE PANEL IS SHOWN @ 120/240 |
| | VTS AND LOAD CALCS FIGS SHOW 230V |
| | AMPERAGES FOR ALL 120V SHOULD REFLECT |
| | 120V AMPERAGE. |
| | |
| | 2)NOTE: PLEASE LIST THE REQ'D ARC FAULT |
| | PROTECTED CIRCUIT(S) PER 210.12 |
| | |
| | 3)NOTE: PLEASE CORRELATE KW RATINGS |
| | FOR NEW AHU. SHOWS 10KW ON A/C PLANS AND |
| | FIGURES TO BE 7.5 KW ON ELECTRICAL LOAD |
| | CALCULATIONS. |
| | |
| | 4)NOTE: PLEASE SEE WATER HEATER, SHOWS |
| | 5KW , W/ 2P 45A BRKR AND #6 AWG. |
| | PLEASE SEE THAT MAX OCP FOR WATER HEATER |
| | IS 150%.MIN 125% 422.13, MAX 150% 422. |
| | 11 |
| | |
| | 5)NOTE: RISER DIAGRAM INDICATES NEW MAIN |
| | YET PLANS ONLY INDICATE A METER SHOWN |
| | ON SIDE OF DWELLING. PLEASE SHOW LOCAT- |
| | -ION OF MAIN. |
| | |
| | 6)NOTE: PLEASE NOTE: THIS IS A NOTE AND |
| | NOT FOR ELECTRICAL PLANS. IF PLANS ARE |
| | SIGNED, DATED AND SEALED BY ARCH, THEN |
| | THOSE PLANS (MECH) MUST CONTAIN SAME |
| | TITLE BLOCK AS SET FORTH ON OTHER SHEETS |
| | AS PER FAC 61G1-16.004. THIS IS ONLY |
| | A NOTE: NOT FOR ELECTRICAL. TITLE BLOCK |
| | IS SHOWN ON ELECTRICAL PLANS CORRECTLY. |
| | |
| | 7)NOTE: PLEASE CLARIFY NEW J-BOX SHOWN |
| | ON RISER, WHAT DOES THIS DO? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |