| Date |
Text |
| 2004-11-23 00:00:00 | ****** UNSAT ******** |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | PLEASE SEE RISER SHOWS 5000A/C?? MIN AIC |
| | IS 10,000 UNLESS USEING CURRENT LIMITING |
| | 5K FUSES. |
| | |
| | 2)NOTE: PLEASE SEE RISER MENTIONS DISC |
| | AS REQUIRED? PLEASE SEE RISER ALSO DOES |
| | NOT INDICATE FEED FROM METER TO MCB |
| | PANEL AS UNDERGROUND. IF THIS FEED IS |
| | NOT IN SLAB, A MAIN DISCONNECTING MEANS |
| | OF SOME SORT WILL BE REQUIRED WITH OCP. |
| | 210.70. |
| | |
| | 3)NOTE: PLEASE SEE LOAD CALCS, THERE ARE |
| | MANY ITEMS ON 20A CIRCUITS WHICH EXCEED |
| | 80% (MAX 1920) ON A 20A BRANCH CIRCUIT. |
| | SOME SHOW 2.2KW? 2.0 KW? ETC |
| | |
| | 4)NOTE: PLEASE VERIFY OCP FOR AHU (8KW) |
| | SHOWN AT 60A'S. MIN OCP PER 424.3B IS |
| | 125%, MAX 150%. |
| | PLEASE ALSO SEE DRYER 5KW ON 40A? |
| | PLEASE VERIFY KW RATING OF WATER HEATER, |
| | THIS DOES NOT SEEM TO BE A COMMON KW? |
| | THIS IS ONLY A NOTE FOR WH. |
| | |
| | 5)NOTE:PLEASE SEE MISSING RECEPT ON 2' |
| | OF WALL IN BEDRM. 210.52 |
| | |
| | 6)NOTE: PLEASE SEE MISSING GFI RECEPT ON |
| | KITCHEN PENINSULAR. 210.52C3, 210.8A6 |
| | |
| | 7)NOTE: PLEASE SEE PANEL SCHEDULE/LOAD |
| | CALCS INDICATES A GARAGE DOOR OPENER? |
| | |
| | 8)NOTE: PLEASE PROVIDE INFORMATION ON |
| | SITE LIGHTING, LANDSCAPE LTS,? POLE |
| | LTS? |
| | IF POLE LTS, THEN PROVIDE WIND LOADING |
| | PER FBC 140 MPH. |
| | |
| | PLEASE SEE ONE SET OF PLANS HAS MOST OF |
| | THE ABOVE ITEMS REDLINED FOR AREAS OF |
| | COMMENTS. |
| | |
| | PLEASE SEE ANY POSSISBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT ONLY NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |