| 2004-02-12 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-PROVIDE COMPLETE PRODUCT APPROVAL FOR |
| | ALL DOOR AND WINDOW TYPES, MULLIONS, |
| | ROOF TILE, FLAT ROOF SYSTEM AND ALL |
| | STRUCTURAL CONNECTORS. |
| | **NOTE: VISIT WWW.FLORIDABUILDING.ORG |
| | FOR OPTIONS AVAILABLE TO PROVIDE THE |
| | PRODUCT APPROVALS. |
| | 2-PROVIDE ENRGY CALCULATIONS AS REQUIRED |
| | BY CHAPTER 13 FBC 2001. |
| | 3-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 4-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| | BRING BACK STAMPED DWGS & PAID RECEIPT |
| | 5-PROVIDE SOIL TEST REPORT. |
| | 6-DESIGN CRITERIA: LIST ALL ITEMS AS |
| | REQ'D BY SEC. 1606.1.7 FBC 2001. |
| | 7-SPECIFY SUPPORTS AND SPACING FOR WWM |
| | IN CONCRETE SLAB. SEE SEC. 1909.3 FBC. |
| | 8-SPECIFY SAFETY GLASS WHERE REQUIRED. |
| | SEE PLANS AND SEC. 2405.2 FBC 2001. |
| | 9-CLARIFY SIZE OF WINDOWS. FLOOR PLAN |
| | CALLS FOR SH245 WINDOWS, WHILE EXT. |
| | ELEVATIONS SHOW 60" HIGH WINDOWS. |
| | ALSO, KEEP IN MIND THAT SH245 WINDOW |
| | MAY NOT PROVIDE THE 24" CLEAR HEIGHT |
| | REQUIRED BY SEC. 1005.4.4 FBC 2001. |
| | 10-PROVIDE DETAIL/SPECS FOR CEILING |
| | INSTALLATION AT ENTRY PORCH, PORTE |
| | COCHERE AND REAR LANAI. SEE ASTM C926 |
| | AND 61063. PROVIDE COMPLETE SPECS |
| | INCLUDING FASTENERS SIZE AND SPACING. |
| | SEC. 2504.2 FBC 2001. |
| | 11-THERE ARE DIFFERENT SPECS FOR ROOF |
| | SHEATHING. CLARIFY WHAT SPECS APPLY TO |
| | THIS PROJECT. SEE SHEETS #3,#7 AND #11 |
| | 12-PROVIDE FRAMING DETAIL/SPECS FOR |
| | ARCHED OPENINGS. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 13-CLARIFY IF USING STORM SHUTTERS OR |
| | MISSILE IMPACT GLAZING IN DOORS AND |
| | WINDOWS. IF USING STORM SHUTTERS, THEN |
| | PROVIDE PRODUCT APPROVAL AND COMPLETE |
| | INFO. INCLUDING COMPLETE INSTALLATION |
| | SCHEDULE, KEY PLAN AND CLEARLY INDICA- |
| | TING ON ENGINEERED DRAWINGS SPECIFIC |
| | ANCHOR TYPE AND SPACING TO BE USED. |
| | 14-DESIGN CRITERIA TO INCLUDE 30PSF |
| | ATTIC LOAD FOR AREAS WITH STORAGE OR |
| | 10PSF FOR AREAS WITHOUT STORAGE. SEE |
| | TABLE 1604.1 FBC 2001. |
| | 15-SHOW LOCATION OF VENTS TO ACHIEVE |
| | ATTIC CROSS VENTILATION. SEC. 2309.7 |
| | FBC 2001. |
| | 16-CLARIFY SPECIFICATIONS FOR WINDOWS & |
| | DOORS BUCK DETAILS. SEE COMMENTS ON |
| | PLANS. CHECK INFO. GIVEN ON DWG #3,#7, |
| | #8. SPECIFY WHICH ONE APPLIES TO THIS |
| | PROJECT. SEC. 104.2.1.2 CITY AMENDMENT |
| | 17-PROVIDE COMPLETE DETAILS/SPECS FOR |
| | SCREENING AT COVERED LANAI OR PROVIDE |
| | COMPLETE INFORMATION UNDER A SEPARATE |
| | PERMIT.SEC. 104.2.1.2 CITY AMENDMENTS. |
| | 18-SHEET #7 ROOF SHEATHING DIAPHRAGM: |
| | REVISE ZONE #3. SEE COMMENTS ON DWG & |
| | FIGURE 1606.2(C) FBC 2001. |
| | 19-SHEET #*: A)REVISE SPECS FOR GARAGE |
| | DOOR. NEED ONE FOR 140MPH, NOT 110MPH. |
| | B)REVISE TIE BEAM ELEVATION. FLAT ROOF |
| | SYSTEM TO HAVE 1/4" PER FT. SLOPE. |
| | SEC. 1508.1 FBC 2001. SEE COOMENTS ON |
| | PLAN. |
| | C)SPECIFY FIREBLOCKING. SEC. 2305 FBC. |
| | D)PROVIDE COMPLETE SPECS FOR FASTENING |
| | OF 2X WOOD LEDGER TO RECEIVE TRUSSES. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | E)CLARIFY SIZE OF GARAGE DOOR. SPECS |
| | CALL FOR 10' WIDE DOOR, BUT PLANS ARE |
| | DIMENSIONED FOR 12'WIDE DOOR. |
| | 20-DETAIL F/11: UPDATE/REVISE SPECS FOR |
| | TRUSS CONNECTOR. HUGHES IS OUT OF |
| | BUSINESS. SEE COMMENTS ON PLANS. |
| | 21-BUILDING VALUATION WAS ADJUSTED TO |
| | $148,670, THEREFORE, ADDITIONAL |
| | FEES MAY BE DUE. |
| | |
| | |
| | NOTES: |
| | **PLEASE RETURN REVIEWED SET AFTER |
| | CORRECTIONS ARE DONE TO ORIGINAL DWGS |
| | TO EXPEDITE REVIEW PROCESS. |
| | **IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 805-6712. |