Plan Review Notes
Plan Review Notes For Permit 04010659
Permit Number 04010659
Review Stop B
Sequence Number 1
Notes
Date Text
2004-02-12 00:00:00BUILDING REVIEW CHECKLIST:
 1-PROVIDE COMPLETE PRODUCT APPROVAL FOR
 ALL DOOR AND WINDOW TYPES, MULLIONS,
 ROOF TILE, FLAT ROOF SYSTEM AND ALL
 STRUCTURAL CONNECTORS.
 **NOTE: VISIT WWW.FLORIDABUILDING.ORG
 FOR OPTIONS AVAILABLE TO PROVIDE THE
 PRODUCT APPROVALS.
 2-PROVIDE ENRGY CALCULATIONS AS REQUIRED
 BY CHAPTER 13 FBC 2001.
 3-NEED RECORDED NOTICE OF COMMENCEMENT.
 4-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DWGS & PAID RECEIPT
 5-PROVIDE SOIL TEST REPORT.
 6-DESIGN CRITERIA: LIST ALL ITEMS AS
 REQ'D BY SEC. 1606.1.7 FBC 2001.
 7-SPECIFY SUPPORTS AND SPACING FOR WWM
 IN CONCRETE SLAB. SEE SEC. 1909.3 FBC.
 8-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2 FBC 2001.
 9-CLARIFY SIZE OF WINDOWS. FLOOR PLAN
 CALLS FOR SH245 WINDOWS, WHILE EXT.
 ELEVATIONS SHOW 60" HIGH WINDOWS.
 ALSO, KEEP IN MIND THAT SH245 WINDOW
 MAY NOT PROVIDE THE 24" CLEAR HEIGHT
 REQUIRED BY SEC. 1005.4.4 FBC 2001.
 10-PROVIDE DETAIL/SPECS FOR CEILING
 INSTALLATION AT ENTRY PORCH, PORTE
 COCHERE AND REAR LANAI. SEE ASTM C926
 AND 61063. PROVIDE COMPLETE SPECS
 INCLUDING FASTENERS SIZE AND SPACING.
 SEC. 2504.2 FBC 2001.
 11-THERE ARE DIFFERENT SPECS FOR ROOF
 SHEATHING. CLARIFY WHAT SPECS APPLY TO
 THIS PROJECT. SEE SHEETS #3,#7 AND #11
 12-PROVIDE FRAMING DETAIL/SPECS FOR
 ARCHED OPENINGS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 13-CLARIFY IF USING STORM SHUTTERS OR
 MISSILE IMPACT GLAZING IN DOORS AND
 WINDOWS. IF USING STORM SHUTTERS, THEN
 PROVIDE PRODUCT APPROVAL AND COMPLETE
 INFO. INCLUDING COMPLETE INSTALLATION
 SCHEDULE, KEY PLAN AND CLEARLY INDICA-
 TING ON ENGINEERED DRAWINGS SPECIFIC
 ANCHOR TYPE AND SPACING TO BE USED.
 14-DESIGN CRITERIA TO INCLUDE 30PSF
 ATTIC LOAD FOR AREAS WITH STORAGE OR
 10PSF FOR AREAS WITHOUT STORAGE. SEE
 TABLE 1604.1 FBC 2001.
 15-SHOW LOCATION OF VENTS TO ACHIEVE
 ATTIC CROSS VENTILATION. SEC. 2309.7
 FBC 2001.
 16-CLARIFY SPECIFICATIONS FOR WINDOWS &
 DOORS BUCK DETAILS. SEE COMMENTS ON
 PLANS. CHECK INFO. GIVEN ON DWG #3,#7,
 #8. SPECIFY WHICH ONE APPLIES TO THIS
 PROJECT. SEC. 104.2.1.2 CITY AMENDMENT
 17-PROVIDE COMPLETE DETAILS/SPECS FOR
 SCREENING AT COVERED LANAI OR PROVIDE
 COMPLETE INFORMATION UNDER A SEPARATE
 PERMIT.SEC. 104.2.1.2 CITY AMENDMENTS.
 18-SHEET #7 ROOF SHEATHING DIAPHRAGM:
 REVISE ZONE #3. SEE COMMENTS ON DWG &
 FIGURE 1606.2(C) FBC 2001.
 19-SHEET #*: A)REVISE SPECS FOR GARAGE
 DOOR. NEED ONE FOR 140MPH, NOT 110MPH.
 B)REVISE TIE BEAM ELEVATION. FLAT ROOF
 SYSTEM TO HAVE 1/4" PER FT. SLOPE.
 SEC. 1508.1 FBC 2001. SEE COOMENTS ON
 PLAN.
 C)SPECIFY FIREBLOCKING. SEC. 2305 FBC.
 D)PROVIDE COMPLETE SPECS FOR FASTENING
 OF 2X WOOD LEDGER TO RECEIVE TRUSSES.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 E)CLARIFY SIZE OF GARAGE DOOR. SPECS
 CALL FOR 10' WIDE DOOR, BUT PLANS ARE
 DIMENSIONED FOR 12'WIDE DOOR.
 20-DETAIL F/11: UPDATE/REVISE SPECS FOR
 TRUSS CONNECTOR. HUGHES IS OUT OF
 BUSINESS. SEE COMMENTS ON PLANS.
 21-BUILDING VALUATION WAS ADJUSTED TO
 $148,670, THEREFORE, ADDITIONAL
 FEES MAY BE DUE.
  
  
 NOTES:
 **PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL DWGS
 TO EXPEDITE REVIEW PROCESS.
 **IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.