| 2004-02-27 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | STRUCTURAL SUBMITTAL ON 2-20-04 FOR |
| | LIGHTING POLE EMBEDMENT CALCULATIONS. |
| | |
| | A) THE SCOPE OF PERMIT# 04010651 WAS |
| | REDUCED TO INCLUDE 'CONDUIT ONLY'.THIS |
| | WAS AGREED WITH C.R. DUNN. TO ALLOW WORK |
| | TO COMMENCE EVENTHOUGH THE SUBMITTED |
| | LIGHTING POLE STRUCTURAL DETAILS WERE |
| | NOT VALID.THOSE STRUCTURAL DETAILS |
| | WERE OMITTED FROM THE PERMIT APPROVED |
| | SET OF PLANS BY REMOVAL OF SHEET 8 OF 11 |
| | PRIOR TO PERMITTING.THE CURRENT |
| | SUBMITTAL OF EMBEDMENT DETAILS MUST BE |
| | SUBMITTED AS A REVISION TO THIS PERMIT |
| | (WITH APPROPRIATE FEE) OR AS A SEPARATE |
| | PERMIT APPLICATION AND SHALL INCLUDE A |
| | A PLAN, WITH SEAL ETC PER COMMENT (B) |
| | BELOW, THAT PROVIDES ALL OF THE |
| | INFORMATION REQUIRED TO ADDRESS COMMENT |
| | #1 FROM THE 1/20/04 PLAN REVIEW (COPY |
| | ATTACHED). |
| | |
| | B) 61G15-23.002(2)FL. ADMIN. CODE. |
| | IT IS NOTED THAT THE EMBEDMENT |
| | CALCULATION COVER SHEET INCLUDES THE |
| | ENGINEER'S SIGNATURE, SEAL, LICENSE # |
| | AND COMPANY ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION #.TO ADDRESS COMMENT #2 |
| | FROM THE 1/20/04 PLAN REVIEW, THAT INFO |
| | SHALL ALSO BE ON THE STRUCTURAL PLAN |
| | REFERENCED IN COMMENT (A) ABOVE. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |