2004-07-07 00:00:00ENTRY DOOR SECOND CHECKLIST:
 1-ARCHITECT TO PROVIDE ALL REQUIREMENTS
 OF CHAPTER 481 FLORIDA STATUTES WHEN
 SUBMITTING INFORMATION FOR PUBLIC
 RECORDS (INFORMATION NEED TO BE IN ALL
 DRAWINGS SUBMITTED).
 2-PROVIDE COMPLETE DESIGN PACKAGE
 INCLUDING SPECIFICATIONS FOR HINGES
 AND LOCKING HARDWARE DESIGNED TO MEET
 THE CALCULATED WIND LOADS. REFERENCE
 SPECIFIC SECTION AND SUBSECTION OF THE
 CODE USED FOR THE DESIGN.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 3-DESIGN PAKCAGE DOESN'T PROVIDE ANY
 SPECIFICATIONS FOR DOOR JAMB AND HOW
 IS IT ATTACHED TO THE STRUCTURAL BUCK.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 4-PROVIDE COMPLETE DOOR DETAILS AND
 SPECS SHOWING GLASS INSTALLATION. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-SPECIFY HOW IS GLASS PROTECTED FROM
 HURRICANE MISSILE IMPACT. DADE COUNTY
 PRODUCT APPROVAL SUBMITTED FOR GLASS
 SAYS NO RATING FOR MISSILE IMPACT.
 6-IF USING STORM SHUTTERS, THEN PROVIDE
 COMPLETE INFORMATION INCLUDING STORM
 SHUTTERS PRODUCT APPROVAL AND HOW IS
 IT INSTALLED.
 7-DADE COUNTY LAMINATED GLASS PRODUCT
 APPROVAL. SEE PAGE 1 OF 1 PRODUCT
 DESCRIPTION LAST NOTE AND PROVIDE
 INFORMATION AS REQUIRED.
 8-SPECIFY HOW IS DOOR MANUFACTURED TO
 COMPLY WITH ENERGY CALCULATIONS.
 WEATHER STRIPPING ETC. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 9-PROVIDE ALL INFORMATION REQUESTED ON
 PROVISO DATED 4-14-04 TO AVOID ANY
 DELAYS OR CONFLICTS DURING INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.