Plan Review Notes
Plan Review Notes For Permit 04010614
Permit Number 04010614
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-23 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE INCLUDE FIRM LICENSE #
 ON TITLE BLOCK AS REQ'D UNDER FS 481.219
 # SHOWN DOES NOT CORRELATE TO DBPR.
  
 2)NOTE: PLEASE SEE MISSING SD OUTSIDE
 BEDROOMS 2,3,4. NFPA-72
  
 3)NOTE: PLEASE SEE LOAD SHOWN FOR GAS
 WATER HEATER AT 2200 VA. PLEASE SEE THAT
 THIS SEEMS A BIT HIGH
  
 4)NOTE: PLEASE SEE A/C SYSTEM #3 IS
 MISSING FROM PANEL SCHEDULES AND FROM
 LOAD CALCULATIONS. ?? PLEASE SEE TOTAL
 LOAD FIGURED FOR SERVICE. IF LOAD FOR
 A/C SYSTEM #3 IS ADDED, IT WILL BE OVER
 THE 200A SERVICE SHOWN. PLEASE ALSO SEE
 THIS WILL LEAVE NO ROOM FOR ANY FUTURE
 LOADS.
  
 5)NOTE: PLEASE SHOW HOW SUB-PANEL IS
 BEING FED??? RISER SHOWS PANEL FROM
 MAIN PANEL, YET NOTHING IS LISTED FOR
 SUB-PANEL ON MAIN PANEL. PLEASE SHOW
 OCP FOR THIS AND PLEASE VERIFY SIZE OF
 CONDUCTORS SHOWN ON RISER FOR 125A PANEL
  
 6)NOTE: PLEASE SEE LOAD FOR WASHER/
 LAUNDRY TO BE A MIN OF 1500 VA.220.16B
  
 7)NOTE: PLEASE SEE PANEL SCHEDULE, ONLY
 SHOWS TWO CIRCUITS FOR ARC FAULT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  