| Plan Review Notes For Permit 04010579 |
| Permit Number |
04010579 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-03-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | CAST IRON SOVENT DESIGN MAN. | | | NUMBER 802 | | | | | | 1) WATER HAMMER ARRESTORS LOCATED AT | | | KITCHEN SINK SHALL BE LOCATED NEAR THE | | | FIXTURES IN AN "EFFECTIVE RANGE" NOT IN | | | THE CEILING AS SHOWN. | | | | | | 2) SHT P-2 SANITARY RISER DIAGRAM FOR | | | THE BATHROOM GROUPS. SOVENT DESIGN CALLS | | | FOR A PRL LINE TO CONNECT TO THE VERTIC- | | | AL PORTION OF THE STACK DOWNSTREAM OF | | | THE OFFSET. A DE-AERATOR FITTING WILL BE | | | REQUIRED AS SHOWN IN ATTACHED SHEET WITH | | | PRL LINE TIED INTO IT. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|