| Plan Review Notes For Permit 04010579 |
| Permit Number |
04010579 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-02-25 00:00:00 | ********** PROVSIO ************** | | | | | | 1)NOTE: PLEASE SEE LOAD FOR LAUNDRY IS | | | SHOWN AT 1200VA, PLEASE SEE 220.16 FOR | | | MIN LOAD TO BE 1500VA. | | | | | | 2)NOTE: PLEASE SEE PLANS SHOW TWO SIZES | | | FOR FEEDERS TO UNIT. ONE NOTE SHOWS 1/0' | | | S AND OTHER #1'S. | | | | | | 3)NOTE: PLEASE CORRELATE VOLTAGE INDICAT | | | -ED FOR PANEL. SHOWN IN LOAD CALCS AND | | | NOTE AS 208, PANEL SHOWS 240V?? | | | | | | PLEASE SUBMIT THE ABOVE AS A REVISION | | | BEFORE ANY ROUGH ELECTRICAL INSPECTION | | | IS CALLED IN. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|