2004-02-25 00:00:00********** PROVSIO **************
  
 1)NOTE: PLEASE SEE LOAD FOR LAUNDRY IS
 SHOWN AT 1200VA, PLEASE SEE 220.16 FOR
 MIN LOAD TO BE 1500VA.
  
 2)NOTE: PLEASE SEE PLANS SHOW TWO SIZES
 FOR FEEDERS TO UNIT. ONE NOTE SHOWS 1/0'
 S AND OTHER #1'S.
  
 3)NOTE: PLEASE CORRELATE VOLTAGE INDICAT
 -ED FOR PANEL. SHOWN IN LOAD CALCS AND
 NOTE AS 208, PANEL SHOWS 240V??
  
 PLEASE SUBMIT THE ABOVE AS A REVISION
 BEFORE ANY ROUGH ELECTRICAL INSPECTION
 IS CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  