Plan Review Notes
Plan Review Notes For Permit 04010579
Permit Number 04010579
Review Stop P
Sequence Number 1
Notes
Date Text
2004-01-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) PLANS TO BE SIGNED WITH A FULL SIG-
 NATURE FROM THE ARCH. PER FS 481.221
 WITH A MINIMUM OF FIRST AND LAST NAME AS
 SHOWN ON ARCH. LICENSE. FAC 61G1-16.003.
 2) SHT P-1 WATER HEATER DETAIL:
 A) THERMAL EXPANSION CONTROL REQUIRED
 PER SECTION 607.3.2
 B) DIELECTRIC UNIONS ARE NOT APPROVED
 FOR WATER PIPING. DELETE FROM DETAIL.
 3) SHT P-2 WATER RISER DIAGRAM: WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS. 604.9
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]