| Plan Review Notes For Permit 04010579 |
| Permit Number |
04010579 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-26 00:00:00 | DENIED: | | | 1.PLAN SHEET M-13 C.U. MOUNTING DETAIL | | | INDICATES 12" FROM THE ROOF SURFACE TO | | | THE BOTTOM OF THE SUPPORT RAIL.SEE THE | | | ATTACHED SCHEDULE FOR HEIGHT REQUIREMENT | | | PER 2001 FBC 1511.7. | | | | | | 2.AUXILIARY DRAIN PAN REQUIRED WITH | | | OVERFLOW PROTECTION BY MEANS OF A FLOAT | | | SWITCH OR A SECONDARY DRAIN TERMINATING | | | AT A CONSPICUOUS POINT TO SERVE AS AN | | | ALARM THAT THE PRIMARY DRAIN IS | | | RESTRICTED.2001 FBC 307.2.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|