2004-01-26 00:00:00DENIED:
 1.PLAN SHEET M-13 C.U. MOUNTING DETAIL
 INDICATES 12" FROM THE ROOF SURFACE TO
 THE BOTTOM OF THE SUPPORT RAIL.SEE THE
 ATTACHED SCHEDULE FOR HEIGHT REQUIREMENT
 PER 2001 FBC 1511.7.
  
 2.AUXILIARY DRAIN PAN REQUIRED WITH
 OVERFLOW PROTECTION BY MEANS OF A FLOAT
 SWITCH OR A SECONDARY DRAIN TERMINATING
 AT A CONSPICUOUS POINT TO SERVE AS AN
 ALARM THAT THE PRIMARY DRAIN IS
 RESTRICTED.2001 FBC 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.