| Plan Review Notes For Permit 04010579 |
| Permit Number |
04010579 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-05 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04010579 | | | ADD: 1801 N FLAGLER# 319 | | | CONT:G C WORKS INC | | | TEL: (305)861-2918 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PLANS ARE TO BE SIGNED WITH A FULL | | | SIGNATURE FROM THE ARCHETECT OF RECORD | | | PER 481.221 WITH A MINIMUM OF FIRST AND | | | LAST NAME AS SHOWN ON THE ARCHITECTS' | | | LICENSE, FAC 61G1-16.003 | | | | | | 2) HI-RISE TYPE II BUILDINGS, 609.2.1 | | | ALL BACKING TO BE FIRE RETARDANT WOOD | | | OR NON-COMBUSTIBLE. | | | | | | 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 4) 104.2.1.3 THE BUILDING OFFICIAL | | | MAY SET STANDARDS THROUGH DEPARTMENTAL | | | POLICY STANDARDS FOR PLANS AND SPRCIFICA | | | TIONS. "NO WHITE OUT". | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|